26
221051B
26
SECTION
Installation
6
s t e p
14
s t e p
15
s t e p
16
Reconnect the violet and red electrical
connections to the fan, the polarity of
the connections is not important.
Reconnect the air pressure switch
tubes.
Loosely fit one extended brass
fluehood/fan assembly screw to the
heat exchanger on the side that the
flue exits. Slide the fluehood/fan
assembly flange under this extended
brass screw whilst turning the
assembly to enable engagement of the
fan outlet extension onto the flue
manifold spigot.
When correctly located, secure the
assembly by fitting the other extended
brass screw and tighten both down.
Secure the flue assembly to the
boiler, using the previously fitted
dogpoint screws noting that these are
keyhole fixings.
Make sure of the correct location of
the flue and boiler.
If removed, refit the control box/
combustion chamber by reversing
the instructions in Section 6, step 18
and Section 10, steps 3,5,6,7 and 9.
2903
FLUE HOOD/
FAN ASSEMBLY
FLUE
MANIFOLD
SPIGOT
FAN
OUTLET
EXTENSION
CLEAR
RED
EXTENDED BRASS
FLUE HOOD FAN
ASSEMBLY SCREW
FAN
OUTLET
EXTENTION
ELECTRICAL
CONNECTION(S)
AIR PRESSURE
SWITCH TUBES