Glow-worm Hideaway 100B Instructions For Use Manual Download Page 11

Supplied By www.heating spares.co  Tel. 0161 620 6677

11

221764B

4  Installation

Diagram 4.5

SECURING THE
THERMOSTAT PHIAL

1870

THERMOSTAT
CAPILLARY

LOCATION
WASHER

PHIAL
POCKET

RETAINING
SPLIT PIN

Diagram 4.4

WATER CONNECTIONS
FULLY PUMPED SYSTEMS

1310

ALTERNATIVE
FLOW
(Must be adjacent
to THERMOSTAT
PHIAL POCKET)

ALTERNATIVE
RETURN
With distributor
tube (not shown)

;;

;;;

;;;

;;;

;;;

;;;

;

Diagram 4.6

PREPARED HOLE IN
THE WALL DIMENSIONS

BALANCED
FLUE DUCT
FROM BOILER

    360

(14

1/

4

 in.)

  485
(19 in.)

PREPARED
HOLE IN
THE WALL

3 (

1/

in.)

MIN.

1384

   360

(14

1/

4

 in.)

When using a rear tapping with Rc1 (1inch BSP) fittings for
28mm o.d. pipework it is recommended that a short nipple and
a R thread (BSP) copper elbow is used.  If the pipework is
required to run back to the wall make sure that it will clear the
boiler air duct and, if working to minimum clearance does not
stick out too far from the boiler, see diagram 4.8.

Make the water connections to the system pipework.

Make the connection to the gas supply at the union gas service
cock.  Test the complete gas installation for soundness and
purge in accordance with the current issue of BS6891.

When the boiler is finally positioned with the balanced flue duct
sticking out into the prepared hole in the wall and pipework
connected, make good to the inside of the wall face around the
boiler flue assembly.

4.8 Balanced Flue Terminal

Take the balanced flue assembly from its carton and remove the
four screws to release the outer baffle, see diagram 4.9.

Remove the four outer wire guards then pull off the inner baffle/
flue duct assembly.

Place the air duct assembly into the prepared hole, from the
outside, engaging it over the boiler air duct.   Slide it until the wall
plate contacts the outer wall surface.

Cut and fix four pieces of the yellow tape provided into the four
corners at the joint in the air duct, running the tape on the inside
of the duct about 25mm (1inch) along the joint from the corners.
Fix four further pieces along the joints overlapping the corner
tapes, to make a good seal.

Cement around the wall plate to make good and provide a
weatherproof seal.

Refit the inner baffle/flue duct assembly over the boiler flue duct
and slide in until the baffle contacts the wire guards.

Seal the flue duct joint on the inside using the semi-transparent,
heat resistant, tape provided, in a similar way to the air duct
sealing procedure, making sure that a good seal is made at the
corners.

Refit the wire guards, outer baffle and secure with the screws
previously removed.

Summary of Contents for Hideaway 100B

Page 1: ...the Heatcall Customer Service number 01773 828100 Our Guarantee gives you peace of mind plus valuable protection against breakdown by covering the cost of Guarantee Registration Balanced Flue Boiler...

Page 2: ...certifiedby Notified body 0086 The CE mark on this appliance shows compliance with 1 Directive 90 396 EEC on the approximation of the laws of the Member States relating to appliances burning gaseous f...

Page 3: ...obtain service please call your installer or Heatcall Glow worm s own service organisation using the telephone number given on the front panel Please be advised that the Benchmark logbook should be co...

Page 4: ...To Turn the Boiler Off For short periods turn the boiler thermostat control knob B anticlockwise to O The pilot will stay alight To relight the main burner turn thermostat control knob B clockwise to...

Page 5: ...millimetres except as noted The Seasonal Efficiency Domestic Boilers UK SEDBUK is 73 0 ThevalueisusedintheUKGovernment sStandardAssessment Procedure SAP for energy rating of dwellings The test data f...

Page 6: ...ast 0 75mm2 24 0 20mm to BS6500 Table 16 must be used for all connections within the boiler casing 1 8 Boiler Location This boiler is not suitable for outside installation The boiler may be installed...

Page 7: ...be connected to a cistern supply with a minimum head of 1 metre 3ft and a maximum of 27 metres 90ft and having an open vent in the system The boiler must not be connected to a sealed water system 2 2...

Page 8: ...plasticguttering or within 450mm 18in of painted eaves or gutter an aluminium shield 1 5 metres 5ft long should be fitted to the underside and immediately beneath the guttering The air inlet products...

Page 9: ...accordance with the Compartment Air Vent Table Boththehighlevelandthelowlevelairventsmustcommunicate with the same room or must both be on the same wall to outside air Before fixing the boiler make s...

Page 10: ...loose items pack see diagram 4 5 4 6 Pump Within Boiler Casing If the pump is to be fitted inside the boiler casing see diagram 6 2 ensure that a heat shield kit is obtained and fitted Kit No 425839...

Page 11: ...tioned with the balanced flue duct sticking out into the prepared hole in the wall and pipework connected make good to the inside of the wall face around the boiler flue assembly 4 8 Balanced Flue Ter...

Page 12: ...ent grille is supplied with the boiler and can be fitted at the rear of the left or right hand side casing The grille is fitted on the opposite side to any pipework connections If required fit the gri...

Page 13: ...AX MIN MID MAX SIDE CASING L H MAX MID MIN MIN BOILER PLINTH FRONT CASING BRACKET MID No 8 SCREW 4 UPPER CASING BRACKET LOCATING LUG AND SLOTS 0886 5 3 Top Casing The top casing can be fitted in four...

Page 14: ...the cable does not touch any hot surfaces 6 2 Pump Cable Connection Heat resistant cable as above must be used if the pump is to be fitted inside the casing SupportthecableinasimilarmannertoControlBo...

Page 15: ...alight repeat the lighting procedure only now keep the control knob pushed for a little longer If the gas control knob A is turned to a safety lock prevents it being turned on again until 3 minutes ha...

Page 16: ...ration screw Relight the main burner and check for gas soundness with a suitable leak detection fluid 7 4 Completion and User Information Instruct and demonstrate the efficient and safe operation of t...

Page 17: ...e and burners to be withdrawn forwards Remove graphite coated nut to release baffle tray and remove from combustion chamber taking care not or damage the insulation material in the sides of the chambe...

Page 18: ...Section 8 1 Disconnect the gas valve plug thermocouple nut and pilot tube connections at the gas valve see diagram 9 1 Support the valve and remove the four right hand flange screws to disconnect the...

Page 19: ...Thermostat Follow the relevant instructions in Section 8 1 Remove the mains inlet connector by pulling downwards see diagram 8 1 Remove the retaining split pin from the phial pocket then withdraw the...

Page 20: ...ntrol box and unhooking at the bottom see diagram 9 4 Pull the ignition lead off piezo unit see diagram 9 4 When refitting control box make sure the thermostat capillary is positioned so that it passe...

Page 21: ...N in inlet connector and gas valve plug terminal N Is there continuity Disconnect ohmmeter and reconnect gas valve plug Restore power to unit Does burner light Boiler in order Isolate electricity sup...

Page 22: ...re the OPEN CIRCUIT voltage Is voltage greater than 15mV Faulty thermocouple Replace Note the open circuit reading then measure the CLOSED CIRCUIT voltage Note this voltage Referring to the diagnosis...

Page 23: ...ACTORY Does pilot flame envelop thermocouple Check aeration If necessary Clean pilot rectify blockage in pilot injector or replace Check thermocouple circuit using Thermocouple and Boiler Overheat Cut...

Page 24: ...British Gas also quote the GC number of the part and appliance 9014 3 5 8 9 10 4 7 6 12 1 2 11 Diagram 11 1 Key No Part No Description GC No 1 203377 Gas control valve 394 151 2 205748 Injector 2 3 2...

Reviews: