The presence detector responds exactly as in normal 

operating mode, only the reaction to brightness/dark-
ness is faster.

 

In order to simulate this behaviour, either the area below 
the presence detector can be illuminated or the blinds 
operated.

 

Test mode ends automatically after 10 min.   
The detector restarts itself (see switch-on behaviour on 
page 10).

 

L

Note: Do not use a torch to switch on the presence 
detector! The adaptive light switching thresholds will be 
distorted!

Factory settings

The presence detector is supplied with the following parame-

ter values:

Parameter

Value

Function C1/C2

Control

Function C3

Control

Light measurement source C3

centre

Terminal S1 assignment

C1

Terminal S2 assignment

C2

Terminal S3/P assignment

Parallel

Brightness set point value C1, C2, C3

500 lux

Room correction factor Win, Mid, Inn, Int

0.3

Detection sensitivity (PIR)

Increment 3

Lighting time delay

10 min

Short presence 

On

Energy saving mode

eco

Switch-on dimming value C1, C2, C3

50 %

Configuration type C1/C2, C3

auto

Control speed

Standard

Minimum dimming value

10 %

Maximum dimming value

100 %

Switching off brightness

10 min

Response after dimming

school

Standby time

0 s

Standby dimming value

10 %

IR group address C1

I

IR group address C2

II

IR group address C3

 III

Scene 1 C1, C2, C3

30 %

Scene 2 C1, C2, C3

70 %

Configuration button/RC

enabled

LED display motion

off

The parameters can only be set to factory settings by using 

the app in combination with the app remote control.

Reset DALI ECGs

The connected DALI ECGs are reset to factory settings and the 

group addresses are deleted.

9.  Start-up

Initial operation (system not configured)

After first switching on the system power supply, the detector 

is restarted, automatically identifies all connected DALI lamps, 

assigns short addresses and manages them in a list. This 

stage is indicated by an LED flashing pattern (5 x on briefly 

every 3 s) and, depending on the size of the system, can last 

up to 3 min.

If no DALI ECG is connected to the detector or a DALI line is 

interrupted, the detector shows this with the LED flashing 

pattern (LED is on and flashes off briefly twice every 3 s). 

If the system is OK, the detector automatically enters con-

figuration mode and waits for configuration of the lighting 

groups. This is indicated by the LED flashing pattern (2 x on 

briefly every 3 s). If configuration has not been carried out the 

system will be in the following operating mode:

 

Detector is in broadcast mode.

 

Function is switching mode (only presence detection, no 
light measurement).

 

All lights are controlled with 100% switching/dimming 
value.

 

The operating mode is as a fully automatic device.

 

All connected buttons are active. It is possible to switch 
on and off, as well as dim.

 

Time delay 10 min.

Configuration of the lighting groups

For the configuration, there are two options available:

 

Using the 

app in combination with the app remote 

control

 

Using the buttons or user remote control

Configuration of the lighting groups by app remote control/

app

y

†

Connect the LMS MG PROGRAM REMOTE BT with the 

Glamox Sensor-app.

y

†

Place the LMS MG PROGRAM REMOTE BT under the detec

-

tor (direct the remote control towards the detector).

y

†

Select type LMS MG PIR CLS SENSOR-R/QA in the app.

y

†

In the „DALI configuration“ menu, select the required group 

assignment.

For the DALI configuration, there are 3 options available:

 

„Group assignment (unaddressed)“: Only DALI ECGs wit

-

hout a group address are processed.

 

„Group assignment (All)“: All connected DALI ECGs are 
configured. 

WARNING

: All existing group assignments 

with group number 1, 2 or 3 will be deleted.

 

„Change group assignment“: The next available ECG will 

be searched for and selected.

 

▻ After selecting the required group assignment, the 

detector is in the programming mode.

 

A DALI lamp starts to pulse (random order).

y

†

Select the desired channel C1, C2 or C3 and assign with   

to the DALI ECG. 

 

▻ The lamp confirms the assignment by dimming to 

20 %.

 

▻ The next DALI lamp starts to pulse. In this way, all of the 

lights are assigned to the lighting groups successively. 

Summary of Contents for B29004001

Page 1: ...REMOTE B29012001 optional app remote control LMS MG PROGRAM REMOTE BT B29012003 optional and the corresponding Glamox Sensor app iOS Android safety cover LMS SENSOR SAFETY COVER B29011001 optional 2 Safety Danger of death through electric shock or fire Installation should only be carried out by a qualified electrician WARNING Work on electrical systems may only be carried out by qualified electric...

Page 2: ...incre ase to 30 minutes or drop back to the set minimum time With settings 2 min or 30 min the time delay remains unchanged at the set value If someone goes into an unoccu pied room only briefly and leaves it within 30 seconds then the lighting will be switched off prematurely after 2 minutes short term presence Push button control The lighting can be manually switched or dimmed at any time at the...

Page 3: ... The detector must not be exposed to direct artificial light Switching operation If the brightness measurement is deactivated the light only comes on when presence is detected brightness setpoint value set to measurement off via the remote control Suitable lamps The presence detector is designed for the operation of fluo rescent lamps compact fluorescent lamps halogen incande scent lamps and LEDs ...

Page 4: ...ia the remote control for support during start up as well as servicing Parameter Description Can be checked via app Can be changed via app Function C1 C2 Function C3 Selection switching control x x Light measurement source C3 Selection Centre Integral x Terminal S1 assignment Terminal S2 assignment Selection C1 C2 C1 C2 C3 C1 C3 C2 C3 C1 C2 C3 x Terminal S3 P assignment Selection Parallel C1 C2 C1...

Page 5: ...inal S2 assignment terminal S3 P assignment Button terminals S1 and S2 can be assigned to the required lighting channel at any time without any need for rewiring Terminal S3 P can be used in two different ways Either buttons or the parallel signal for master master parallel switching can be connected The required assignment is car ried out via the parameter Terminal S3 P assignment Value range Gla...

Page 6: ... The brightness measurement value appears in the display Important Press the send button drücken After this the brightness measurement is calibrated The calculated room correction factor is adopted For monitoring purposes the room correction factor via para meters Room correction factor Win Room correction factor mid or Room correction factor opposite to window can be queried The standard value is...

Page 7: ...r app Constant light control remains active temporarily after manual dimming to the current brightness value as the new setpoint value After the lighting time delay has expired the originally configured setpoint value is restored office Constant light control is interrupted temporarily via manual dim ming The set point value remains unchanged school Further information can be found in the chapter ...

Page 8: ...scription Can be triggered via app Switching light C3 Lighting group C3 can be switched on and off x Switching light All All lighting groups can be switched on and off together x Teach in channel C1 Lighting channel C1 execution x Teach in channel C2 Lighting channel C2 execution x Teach in channel C3 Lighting channel C3 execution x Teach in channel C1 C2 C3 Activate for all lighting channels C1 C...

Page 9: ...e size of the system can last up to 3 min If no DALI ECG is connected to the detector or a DALI line is interrupted the detector shows this with the LED flashing pattern LED is on and flashes off briefly twice every 3 s If the system is OK the detector automatically enters con figuration mode and waits for configuration of the lighting groups This is indicated by the LED flashing pattern 2 x on br...

Page 10: ...ontrol com mands in the app If the lighting group needs to be changed on individual DALI ECGs DALI configuration can be carried out using the app via Change group assignment When using the button the whole DALI configuration must be carried out again Switch on behaviour configured systems Every time the power supply is switched on the presence detector runs through two phases that are indicated by...

Page 11: ...on Terminal S3 P assignment parameter set to Parallel Lighting does not react Short circuit or interruption in the DALI bus Electri cal surge in the DALI bus Disconnect the detector from the supply network for 1 minute thermal fuse Error flashing 4 x per second Error in self test device not properly functional LED is on and flashes off briefly 2 x every 3 s Detector does not recognise DALI ECGs Ch...

Reviews: