Master/master parallel switching

Several masters can be used in parallel switching. Each 

master controls its lighting groups according to its own 

brightness measurements. Time delays and brightness 

setpoint values are set individually on each master. Presence 

continues to be detected by all detectors. 

Master

DALI

DALI

DA+ DA–

S1 S2

S3/P

N

L

N

L

EVG

Master

DA+ DA–

S1 S2

S3/P

N

L

EVG

 

Master with 2 lighting groups and individual brightness 
measurement

 

Switch up to 10 detectors in parallel

 

Use the same phase for all detectors and buttons

8.  Settings

The presence detectors are supplied with basic settings ready 

for operation. The specifications are guidance values. The app 

remote control LMS MG PROGRAM REMOTE BT in combination 

with the Glamox Sensor-app is available for start-up support. 

They enable remote setting. The parameters can be queried, 

adjusted and optimised. A range of variable parameters is 

available for adjustment with the remote control (see section 

“Parameters via remote control”).

Settings via the button 

Pressing any button for longer than 15 s triggers the teach-in 

of the brightness setpoint value by the teach-in function. In 

addition, the teach-in function can be conveniently executed 

via app in combination with the app remote control LMS MG 

PROGRAM REMOTE BT (see section “Control commands via 

remote control”, page 8).

The teach-in function via the button can be disabled using 

the app when the <Configuration button/RC> parameter is 

set to “disabled”.

The lighting groups can also be configured using the but

-

tons. All connected buttons can be used for configuration. 

A detailed description can be found in chapter „9. Start-up“ 

(page 9).

Configuration via the buttons can be disabled via app in com

-

bination with the app remote control when the <Configuration 

button/RC> parameter is set to “disabled”.

Parameters via remote control

The following parameters can be checked or changed via 

the remote control for support during start-up as well as 

servicing:

Parameter

Description

Can be 

checked 

via app

Can be 

changed 

via app

Function C1/C2

Function C3

Selection: switching/

control

x

x

Light measurement 

source C3

Selection: Centre/

Integral

x

Terminal S1 assignment

Terminal S2 assignment

Selection: C1/C2/

C1+C2/C3/C1+C3/

C2+C3/C1+C2+C3

x

Terminal S3/P 

assignment

Selection: Parallel/C1/

C2/C1+C2/C3/C1+C3/

C2+C3/C1+C2+C3

x

Brightness set point value 

C1, C2, C3

Value range in lux/

measurement off

x

x

Brightness actual value 

C1, C2, C3

Query brightness actual 

value

x

Room correction factor 

Win

Room correction factor 

on side towards window

x

x

Brightness measurement 

value Win

Lux meter brightness 

value on side towards 

window in lux

x

Room correction factor 

Mid

Room correction factor 

middle

x

x

Brightness measurement 

value Mid

Lux meter brightness 

value middle in lux

x

Room correction factor 

Inn

Room correction factor 

Inn

x

x

Brightness measurement 

value Ins

Lux meter brightness 

value interior in lux

x

Room correction factor Int Room correction factor 

Integral

x

x

Brightness measurement 

value Int

Lux meter brightness 

value Integral in lux

x

Detection sensitivity (PIR)

Value range in 

increments

x

x

Lighting time delay

Value range in seconds 

and minutes

x

Short presence

Short-term presence: 

On/Off

x

x

Energy saving mode

Selection: eco/eco plus

x

x

Switch-on dimming value 

C1, C2, C3

Value range in %

x

Configuration type C1/C2

 

Configuration type C3

Selection: auto/man

x

x

Control speed

Selection: standard/

medium/fast

x

Minimum dimming value

Value range in %

x

Maximum dimming value

Value range in %

x

Switching off brightness

Value range in minutes/

hours/never off

x

Manual dimming 

response

Selection: school/office

x

Standby time

Value range in seconds/

minutes/Permanently 

on

x

Standby dimming value

Value range in %

x

IR group address C1,  

IR group address C2,  

IR group address C3

Selection: All/I/II/III 

(App to VIII)

x

Scene 1 C1

Scene 2 C1

Scene for lighting chan-

nel C1 value range in %

x

Scene 1 C2

Scene 2 C2

Scene for lighting chan-

nel C2 value range in %

x

Scene 1 C3

Scene 2 C3

Scene for lighting chan-

nel C3 value range in %

x

Summary of Contents for B29004001

Page 1: ...REMOTE B29012001 optional app remote control LMS MG PROGRAM REMOTE BT B29012003 optional and the corresponding Glamox Sensor app iOS Android safety cover LMS SENSOR SAFETY COVER B29011001 optional 2 Safety Danger of death through electric shock or fire Installation should only be carried out by a qualified electrician WARNING Work on electrical systems may only be carried out by qualified electric...

Page 2: ...incre ase to 30 minutes or drop back to the set minimum time With settings 2 min or 30 min the time delay remains unchanged at the set value If someone goes into an unoccu pied room only briefly and leaves it within 30 seconds then the lighting will be switched off prematurely after 2 minutes short term presence Push button control The lighting can be manually switched or dimmed at any time at the...

Page 3: ... The detector must not be exposed to direct artificial light Switching operation If the brightness measurement is deactivated the light only comes on when presence is detected brightness setpoint value set to measurement off via the remote control Suitable lamps The presence detector is designed for the operation of fluo rescent lamps compact fluorescent lamps halogen incande scent lamps and LEDs ...

Page 4: ...ia the remote control for support during start up as well as servicing Parameter Description Can be checked via app Can be changed via app Function C1 C2 Function C3 Selection switching control x x Light measurement source C3 Selection Centre Integral x Terminal S1 assignment Terminal S2 assignment Selection C1 C2 C1 C2 C3 C1 C3 C2 C3 C1 C2 C3 x Terminal S3 P assignment Selection Parallel C1 C2 C1...

Page 5: ...inal S2 assignment terminal S3 P assignment Button terminals S1 and S2 can be assigned to the required lighting channel at any time without any need for rewiring Terminal S3 P can be used in two different ways Either buttons or the parallel signal for master master parallel switching can be connected The required assignment is car ried out via the parameter Terminal S3 P assignment Value range Gla...

Page 6: ... The brightness measurement value appears in the display Important Press the send button drücken After this the brightness measurement is calibrated The calculated room correction factor is adopted For monitoring purposes the room correction factor via para meters Room correction factor Win Room correction factor mid or Room correction factor opposite to window can be queried The standard value is...

Page 7: ...r app Constant light control remains active temporarily after manual dimming to the current brightness value as the new setpoint value After the lighting time delay has expired the originally configured setpoint value is restored office Constant light control is interrupted temporarily via manual dim ming The set point value remains unchanged school Further information can be found in the chapter ...

Page 8: ...scription Can be triggered via app Switching light C3 Lighting group C3 can be switched on and off x Switching light All All lighting groups can be switched on and off together x Teach in channel C1 Lighting channel C1 execution x Teach in channel C2 Lighting channel C2 execution x Teach in channel C3 Lighting channel C3 execution x Teach in channel C1 C2 C3 Activate for all lighting channels C1 C...

Page 9: ...e size of the system can last up to 3 min If no DALI ECG is connected to the detector or a DALI line is interrupted the detector shows this with the LED flashing pattern LED is on and flashes off briefly twice every 3 s If the system is OK the detector automatically enters con figuration mode and waits for configuration of the lighting groups This is indicated by the LED flashing pattern 2 x on br...

Page 10: ...ontrol com mands in the app If the lighting group needs to be changed on individual DALI ECGs DALI configuration can be carried out using the app via Change group assignment When using the button the whole DALI configuration must be carried out again Switch on behaviour configured systems Every time the power supply is switched on the presence detector runs through two phases that are indicated by...

Page 11: ...on Terminal S3 P assignment parameter set to Parallel Lighting does not react Short circuit or interruption in the DALI bus Electri cal surge in the DALI bus Disconnect the detector from the supply network for 1 minute thermal fuse Error flashing 4 x per second Error in self test device not properly functional LED is on and flashes off briefly 2 x every 3 s Detector does not recognise DALI ECGs Ch...

Reviews: