~40°

~1,8 m

~1,8 m

~40°

1,5 x 3,5 m

2 x 3,5 m

1,5 x 3,5 m

Installation height 3 m

Figure at table height (0,8 m)

LMS MG PROGRAM REMOTE BT

 

or Lux meter

Room correction factor = Brightness value at the ceiling

 

 

Brightness value on the work surface

The brightness measurement value at the ceiling is influenced 

by the installation location, incidence of light, position of the 

sun, weather conditions, the reflection properties of the room, 

and the furniture. In order to be able to adhere to the requi

-

red lux value in the desired area, a comparison of the bright

-

ness measurements is necessary. The measured lux meter 

value 

 below the presence detector is sent to the detector 

via the remote control. When sending the brightness measu-

rement value, the room correction factor of the corresponding 

lighting channel is automatically adjusted to the conditions 

inside the room. Two different procedures can be selected for 

the comparison.

y

†

Connect the Glamox Sensor-app with the app remote con

-

trol LMS MG PROGRAM REMOTE BT.

y

†

Select detector type <LMS MG PIR CLS SENSOR-R/QA> and 

load the parameter set.

y

†

Select the parameter <Brightness measurement value Win>, 

<Brightness measurement value Mid> or <Brightness mea-

surement value Ins> anwählen.

Automatic calibration

y

†

Set up the LMS MG PROGRAM REMOTE BT according to 

the drawing, and move a few steps away from the mea-

surement location, so the lux measurement will not be 

influenced.

y

†

Press OK.

 

A new window with the measured brightness measu-
rement value is shown. If you would like to apply this 
value

y

†

Press OK.

y

†

Important: Press the send button ( ) drücken. After this, 

the brightness measurement is calibrated.

Manual calibration with additional lux meter

y

†

Set up or align the lux meter according to the drawing, and 

read the lux value.

y

†

Press „Enter“ in the app.

 

A new window opens.

y

†

Enter the lux value and press OK.

 

The brightness measurement value appears in the 
display.

y

†

Important: Press the send button ( ) drücken. After this, 

the brightness measurement is calibrated.

 

The calculated room correction factor is adopted. For 

monitoring purposes the room correction factor via para-

meters <Room correction factor Win>, <Room correction 

factor mid> or <Room correction factor opposite to 

window> can be queried. The standard value is 0.3.

Detection sensitivity

The detector has 5 sensitivity increments. The basic setting is 

the middle increment (3). 

Increments 1 to 5 can be selected and sent to the detector 

with the app in combination with the app remote control.

Value range

Increment Sensitivity
1

Very insensitive

2

Insensitive

3

Standard

4

Sensitive

5

Very sensitive

By selecting the test presence operating mode, the set sensi-

tivity increment is not changed. 

Lighting time delay

The time delay applies jointly to all lighting channels.

Value range (Glamox Sensor-app)

Lighting time delay C1, C2, C3

10 s–60 min

Short presence

If someone goes into an unoccupied room only briefly and 

leaves it within 30 seconds, then the lighting will be switched 

off prematurely after 2 minutes (short-term presence). The 

short-term presence can be used for the fully automatic and 

semi-automatic configuration types.

Value range (Glamox Sensor-app)

The time delay is applied according to the set time delay.

Off

Short-term presence is active.

On

Energy saving mode eco/eco plus

The selection of “eco” stands for optimum switching behavi-

our, while “eco plus” stands for maximum energy saving.

Value range (Glamox Sensor-app)

“eco”

The time delay adjusts to the user behaviour by self-learning. 

It does not drop below the set value.

“eco plus” The set time delay remains unchanged (no self-learning 

effect). Faster response to brightness detection than with 

“eco”.

Switch-on dimming value C1, C2, C3

In switching mode and in the constant light control function, 

the lighting is switched on with the switch-on dimming value.

Value range (Glamox Sensor-app)

Switch-on dimming value C1, C2, C3

30–100 %

Summary of Contents for B29004001

Page 1: ...REMOTE B29012001 optional app remote control LMS MG PROGRAM REMOTE BT B29012003 optional and the corresponding Glamox Sensor app iOS Android safety cover LMS SENSOR SAFETY COVER B29011001 optional 2 Safety Danger of death through electric shock or fire Installation should only be carried out by a qualified electrician WARNING Work on electrical systems may only be carried out by qualified electric...

Page 2: ...incre ase to 30 minutes or drop back to the set minimum time With settings 2 min or 30 min the time delay remains unchanged at the set value If someone goes into an unoccu pied room only briefly and leaves it within 30 seconds then the lighting will be switched off prematurely after 2 minutes short term presence Push button control The lighting can be manually switched or dimmed at any time at the...

Page 3: ... The detector must not be exposed to direct artificial light Switching operation If the brightness measurement is deactivated the light only comes on when presence is detected brightness setpoint value set to measurement off via the remote control Suitable lamps The presence detector is designed for the operation of fluo rescent lamps compact fluorescent lamps halogen incande scent lamps and LEDs ...

Page 4: ...ia the remote control for support during start up as well as servicing Parameter Description Can be checked via app Can be changed via app Function C1 C2 Function C3 Selection switching control x x Light measurement source C3 Selection Centre Integral x Terminal S1 assignment Terminal S2 assignment Selection C1 C2 C1 C2 C3 C1 C3 C2 C3 C1 C2 C3 x Terminal S3 P assignment Selection Parallel C1 C2 C1...

Page 5: ...inal S2 assignment terminal S3 P assignment Button terminals S1 and S2 can be assigned to the required lighting channel at any time without any need for rewiring Terminal S3 P can be used in two different ways Either buttons or the parallel signal for master master parallel switching can be connected The required assignment is car ried out via the parameter Terminal S3 P assignment Value range Gla...

Page 6: ... The brightness measurement value appears in the display Important Press the send button drücken After this the brightness measurement is calibrated The calculated room correction factor is adopted For monitoring purposes the room correction factor via para meters Room correction factor Win Room correction factor mid or Room correction factor opposite to window can be queried The standard value is...

Page 7: ...r app Constant light control remains active temporarily after manual dimming to the current brightness value as the new setpoint value After the lighting time delay has expired the originally configured setpoint value is restored office Constant light control is interrupted temporarily via manual dim ming The set point value remains unchanged school Further information can be found in the chapter ...

Page 8: ...scription Can be triggered via app Switching light C3 Lighting group C3 can be switched on and off x Switching light All All lighting groups can be switched on and off together x Teach in channel C1 Lighting channel C1 execution x Teach in channel C2 Lighting channel C2 execution x Teach in channel C3 Lighting channel C3 execution x Teach in channel C1 C2 C3 Activate for all lighting channels C1 C...

Page 9: ...e size of the system can last up to 3 min If no DALI ECG is connected to the detector or a DALI line is interrupted the detector shows this with the LED flashing pattern LED is on and flashes off briefly twice every 3 s If the system is OK the detector automatically enters con figuration mode and waits for configuration of the lighting groups This is indicated by the LED flashing pattern 2 x on br...

Page 10: ...ontrol com mands in the app If the lighting group needs to be changed on individual DALI ECGs DALI configuration can be carried out using the app via Change group assignment When using the button the whole DALI configuration must be carried out again Switch on behaviour configured systems Every time the power supply is switched on the presence detector runs through two phases that are indicated by...

Page 11: ...on Terminal S3 P assignment parameter set to Parallel Lighting does not react Short circuit or interruption in the DALI bus Electri cal surge in the DALI bus Disconnect the detector from the supply network for 1 minute thermal fuse Error flashing 4 x per second Error in self test device not properly functional LED is on and flashes off briefly 2 x every 3 s Detector does not recognise DALI ECGs Ch...

Reviews: