10
•
In the case of group assignment (Unadressed) or (All):
If all DALI EBs are assigned to a lighting group, the
detector terminates the configuration process and
restarts (startup phase of 30 s). The detector then
switches to the normal operating mode and the
configuration is completed.
L
If necessary, the configuration process can be ended by
pressing „End“ .
▻
In this case, the system is not ready for operation.
•
If „Change group assignment“ has been selected, it is
possible to switch with „Continue“ o the next DALI-ECG
without changing the lighting group.
y
When all required changes have been made, complete the
configuration by pressing „End“.
Configuration of the lighting groups using buttons
For the configuration using buttons, the <Configuration
button/RC> parameter must be set to „enabled“. All connec-
ted buttons can be used for configuration.
L
If button S3 is used, the <Terminal S3/P assignment>
parameter may not be set to „Parallel“.
•
DALI configuration is started by briefly pressing any
button 5 x (<0.4 s) followed by 1 x long press (> 15 s).
The LED is switched off.
▻
A DALI lamp starts to pulse (random order).
•
The lighting group is assigned by pressing the corres-
ponding button:
y
y
1 x short button push = Channel C1
y
y
2 x short button push = Channel C2
y
y
3 x short button push = Channel C3
▻ The lamp confirms the assignment by dimming to 20 %
(3 s after the last button push).
▻ The next DALI lamp starts to pulse. In this way, all of the
lights are assigned to the lighting groups successively.
•
When all DALI-ECGs have an assigned lighting group, the
detector automatically ends configuration and restarts
itself, see section „Switching behaviour“. Finally, the
detector enters normal operation and configuration is
complete.
•
If so required the configuration can be ended by pressing
any button for longer than 15 s. The detector restarts
itself. In this case, the system will not be ready for use
and must be reconfigured.
L
Instead of the button, configuration can also be carried out
using the On/Off buttons on LMS MG PROGRAM REMOTE
BT/LMS MG USER REMOTE.
Checking the configuration
The lighting group assignment can be checked at any time
using the buttons or the remote control, in that the individual
lighting groups are switched on or off (menu „Control com-
mands“ in the app).
If the lighting group needs to be changed on individual DALI
ECGs, DALI configuration can be carried out using the app
via „Change group assignment“. When using the button, the
whole DALI configuration must be carried out again.
Switch-on behaviour (configured systems)
Every time the power supply is switched on, the presence
detector runs through two phases that are indicated by the
LED:
1. Start-up phase (30 s)
•
The red LED flashes at one second intervals and lighting
is switched on with switch-on dimming value.
•
The detector does not respond to push-button com-
mands or to remote controls.
•
The lighting is switched off after 30 s when the room is
unoccupied.
2. Operation
•
The red LED is off. The constant light control or switching
mode are started.
•
The detector is ready for operation.
10. Technical data
Operating voltage
110–230 V AC, +10 %/–15 %
Frequency
50–60 Hz
Upstream protection device:
16 A
Power consumption (without DALI-ECG)
< 0.4 W
Type of installation
Ceiling installation; flush/surface
mounted or ceiling installation
Recommended installation height
2.0–3.5 m/max. 10 m
Minimum height
> 1.7 m
Detection area
horizontal 360°
Maximum range
Ø 7 m (Mh. 3.5 m)/38 m
2
seated
Ø 25 m (Mh. 10 m)/491 m
2
walking
Setting range brightness setpoint value
10–3000 lux
Lighting time delay
10 s–60 min
Lighting standby time
0 s–60 min/permanently on
Standby dimming value
1–25 %
Control output lighting
DALI interface 100 mA, max. 50
DALI devices, base insulation
Connection type
Screw terminals
Max. cable cross-section
Max. 2 x 2.5 mm²
Size of flush-mounted box
Size 1, Ø 55 mm (NIS, PMI)
Protection rating
IP 54 installed
Ambient temperature
–15 °C … +50 °C
CE Declaration of Conformity
This device conforms to the safety
regulations of the EMC directive
2014/30/EU and of directive
2014/35/EU.
Troubleshooting
Fault
Cause
Light does not switch
on and/or off if pre-
sence is detected and
in darkness
Brightness setpoint value is set too low; detector
set on semi-automatic; light was switched off
manually via button, LMS MG USER REMOTE or
LMS MG PROGRAM REMOTE BT; person not within
detection area; obstruction(s) interrupting detec-
tion; time delay set too short
Light stays on with
detection of presence
despite sufficient
brightness
Brightness setpoint value is set too high; light was
briefly switched on manually via button, LMS MG
USER REMOTE or LMS MG PROGRAM REMOTE BT
(wait 30 min in switching operation); detector is in
test mode