In the case of group assignment (Unadressed) or (All): 

 

If all DALI EBs are assigned to a lighting group, the 

detector terminates the configuration process and 

restarts (startup phase of 30 s). The detector then  
switches to the normal operating mode and the  

configuration is completed.

 

L

If necessary, the configuration process can be ended by 

pressing „End“ .

 

In this case, the system is not ready for operation.

 

If „Change group assignment“ has been selected, it is 

possible to switch with „Continue“ o the next DALI-ECG 

without changing the lighting group.

y

†

When all required changes have been made, complete the 

configuration by pressing „End“.

Configuration of the lighting groups using buttons

For the configuration using buttons, the <Configuration 

button/RC> parameter must be set to „enabled“. All connec-

ted buttons can be used for configuration.

 

L

If button S3 is used, the <Terminal S3/P assignment> 
parameter may not be set to „Parallel“. 

 

DALI configuration is started by briefly pressing any 
button 5 x (<0.4 s) followed by 1 x long press (> 15 s). 

The LED is switched off.

 

A DALI lamp starts to pulse (random order).

 

The lighting group is assigned by pressing the corres-
ponding button:

y

y

1 x short button push = Channel C1

y

y

2 x short button push = Channel C2

y

y

3 x short button push = Channel C3

 

▻ The lamp confirms the assignment by dimming to 20 % 

(3 s after the last button push). 

 

▻ The next DALI lamp starts to pulse. In this way, all of the 

lights are assigned to the lighting groups successively. 

 

When all DALI-ECGs have an assigned lighting group, the 
detector automatically ends configuration and restarts 

itself, see section „Switching behaviour“. Finally, the 

detector enters normal operation and configuration is 

complete.

 

If so required the configuration can be ended by pressing 

any button for longer than 15 s. The detector restarts 
itself. In this case, the system will not be ready for use 

and must be reconfigured.

 

L

Instead of the button, configuration can also be carried out 
using the On/Off buttons on LMS MG PROGRAM REMOTE 
BT/LMS MG USER REMOTE.

Checking the configuration

The lighting group assignment can be checked at any time 

using the buttons or the remote control, in that the individual 

lighting groups are switched on or off (menu „Control com-

mands“ in the app).

If the lighting group needs to be changed on individual DALI 

ECGs, DALI configuration can be carried out using the app 

via „Change group assignment“. When using the button, the 

whole DALI configuration must be carried out again.

Switch-on behaviour (configured systems)

Every time the power supply is switched on, the presence 

detector runs through two phases that are indicated by the 

LED:

1. Start-up phase (30 s)

 

The red LED flashes at one second intervals and lighting 

is switched on with switch-on dimming value.

 

The detector does not respond to push-button com-
mands or to remote controls.

 

The lighting is switched off after 30 s when the room is 
unoccupied.

2. Operation

 

The red LED is off. The constant light control or switching 
mode are started.

 

The detector is ready for operation.

10. Technical data

Operating voltage

110–230 V AC, +10 %/–15 %

Frequency

50–60 Hz

Upstream protection device:

16 A

Power consumption (without DALI-ECG)

< 0.4 W

Type of installation

Ceiling installation; flush/surface 

mounted or ceiling installation

Recommended installation height

2.0–3.5 m/max. 10 m

Minimum height

> 1.7 m

Detection area 

horizontal 360°

Maximum range

Ø 7 m (Mh. 3.5 m)/38 m

2

 seated

Ø 25 m (Mh. 10 m)/491 m

2

 

walking

Setting range brightness setpoint value

10–3000 lux

Lighting time delay

10 s–60 min

Lighting standby time

0 s–60 min/permanently on

Standby dimming value

1–25 %

Control output lighting

DALI interface 100 mA, max. 50 

DALI devices, base insulation

Connection type

Screw terminals

Max. cable cross-section

Max. 2 x 2.5 mm²

Size of flush-mounted box

Size 1, Ø 55 mm (NIS, PMI)

Protection rating

IP 54 installed

Ambient temperature

–15 °C … +50 °C

CE Declaration of Conformity

This device conforms to the safety 

regulations of the EMC directive 

2014/30/EU and of directive 

2014/35/EU. 

Troubleshooting

Fault

Cause

Light does not switch 

on and/or off if pre-

sence is detected and 

in darkness

Brightness setpoint value is set too low; detector 

set on semi-automatic; light was switched off 

manually via button, LMS MG USER REMOTE or 

LMS MG PROGRAM REMOTE BT; person not within 

detection area; obstruction(s) interrupting detec-

tion; time delay set too short

Light stays on with 

detection of presence 

despite sufficient 

brightness 

Brightness setpoint value is set too high; light was 

briefly switched on manually via button, LMS MG 

USER REMOTE or LMS MG PROGRAM REMOTE BT 

(wait 30 min in switching operation); detector is in 

test mode

Summary of Contents for B29004001

Page 1: ...REMOTE B29012001 optional app remote control LMS MG PROGRAM REMOTE BT B29012003 optional and the corresponding Glamox Sensor app iOS Android safety cover LMS SENSOR SAFETY COVER B29011001 optional 2 Safety Danger of death through electric shock or fire Installation should only be carried out by a qualified electrician WARNING Work on electrical systems may only be carried out by qualified electric...

Page 2: ...incre ase to 30 minutes or drop back to the set minimum time With settings 2 min or 30 min the time delay remains unchanged at the set value If someone goes into an unoccu pied room only briefly and leaves it within 30 seconds then the lighting will be switched off prematurely after 2 minutes short term presence Push button control The lighting can be manually switched or dimmed at any time at the...

Page 3: ... The detector must not be exposed to direct artificial light Switching operation If the brightness measurement is deactivated the light only comes on when presence is detected brightness setpoint value set to measurement off via the remote control Suitable lamps The presence detector is designed for the operation of fluo rescent lamps compact fluorescent lamps halogen incande scent lamps and LEDs ...

Page 4: ...ia the remote control for support during start up as well as servicing Parameter Description Can be checked via app Can be changed via app Function C1 C2 Function C3 Selection switching control x x Light measurement source C3 Selection Centre Integral x Terminal S1 assignment Terminal S2 assignment Selection C1 C2 C1 C2 C3 C1 C3 C2 C3 C1 C2 C3 x Terminal S3 P assignment Selection Parallel C1 C2 C1...

Page 5: ...inal S2 assignment terminal S3 P assignment Button terminals S1 and S2 can be assigned to the required lighting channel at any time without any need for rewiring Terminal S3 P can be used in two different ways Either buttons or the parallel signal for master master parallel switching can be connected The required assignment is car ried out via the parameter Terminal S3 P assignment Value range Gla...

Page 6: ... The brightness measurement value appears in the display Important Press the send button drücken After this the brightness measurement is calibrated The calculated room correction factor is adopted For monitoring purposes the room correction factor via para meters Room correction factor Win Room correction factor mid or Room correction factor opposite to window can be queried The standard value is...

Page 7: ...r app Constant light control remains active temporarily after manual dimming to the current brightness value as the new setpoint value After the lighting time delay has expired the originally configured setpoint value is restored office Constant light control is interrupted temporarily via manual dim ming The set point value remains unchanged school Further information can be found in the chapter ...

Page 8: ...scription Can be triggered via app Switching light C3 Lighting group C3 can be switched on and off x Switching light All All lighting groups can be switched on and off together x Teach in channel C1 Lighting channel C1 execution x Teach in channel C2 Lighting channel C2 execution x Teach in channel C3 Lighting channel C3 execution x Teach in channel C1 C2 C3 Activate for all lighting channels C1 C...

Page 9: ...e size of the system can last up to 3 min If no DALI ECG is connected to the detector or a DALI line is interrupted the detector shows this with the LED flashing pattern LED is on and flashes off briefly twice every 3 s If the system is OK the detector automatically enters con figuration mode and waits for configuration of the lighting groups This is indicated by the LED flashing pattern 2 x on br...

Page 10: ...ontrol com mands in the app If the lighting group needs to be changed on individual DALI ECGs DALI configuration can be carried out using the app via Change group assignment When using the button the whole DALI configuration must be carried out again Switch on behaviour configured systems Every time the power supply is switched on the presence detector runs through two phases that are indicated by...

Page 11: ...on Terminal S3 P assignment parameter set to Parallel Lighting does not react Short circuit or interruption in the DALI bus Electri cal surge in the DALI bus Disconnect the detector from the supply network for 1 minute thermal fuse Error flashing 4 x per second Error in self test device not properly functional LED is on and flashes off briefly 2 x every 3 s Detector does not recognise DALI ECGs Ch...

Reviews: