Brightness measurement

The presence detector measures artifi cial light and daylight 

by means of three directed light measurements. The central 

light measurement detects the brightness directly below the 

detector (A), while the two other light measurements detect 

the brightness close to the window (B) or in the interior (C). 

The installation location is the reference point for the lighting 

level. The brightness measurement can be adapted to the 

conditions in a room with the room correction factor. 

~ 1,8 m

~ 1,8 m

1

C

B

A

Each light measurement area maps a rectangle of about 2.0 x 

3.5 m at table height. Depending on the operating mode, the 

light measurements are assigned as followed:

 

2-channel: Window light measurement (B) is perma-
nently assigned to lighting channel C1 and interior light 
measurement (C) to lighting channel C2

 

3-channel: As with 2-channel, but with free choice 
between central light measurement (A) and integral light 
measurement (average of light measurements A + B + C) 
in the case of lighting channel C3

Switching

Direct light infl uences the light measurement. Avoid placing 

fl oor lamps or suspended lighting directly below the detector.

Constant light control

The detector must be positioned in such a way that it only 

detects artifi cial light that it controls itself. Artifi cial light that 

is controlled by other detectors or manually switched work 

lighting infl uence the brightness measurement of the detec-

tor. The detector must not be exposed to direct artifi cial light.

Switching operation

If the brightness measurement is deactivated, the light only 

comes on when presence is detected (brightness setpoint 

value set to “measurement off” via the remote control).

Suitable lamps

The presence detector is designed for the operation of fl uo-

rescent lamps, compact fl uorescent lamps, halogen/incande-

scent lamps and LEDs.

6.   Installation

 

L

Note window/interior alignment!

Flush-mounted fi tting

The presence detector is fl ush-mounted using a size 1 stan-

dard fl ush-mounting installation socket.

Surface-mounted installation

A back box LMS MG SURFACE MNT FRAME (B29011002) is 

available for surface mounted installation.

7.  Connection

The presence detectors can be combined as master in indi-

vidual switching or as master/master in parallel switching. 

Several push buttons can be connected to one control input. 

Illuminated push buttons can only be used with neutral con-

ductor connection. 

With the app in combination with app remote control lighting 

channels C1 to C3 can be assigned to the required button 

inputs S1 to S3 via the parameter <Terminal SX assignment>. 

The input S3/P can be used for the master/master switching, 

or as button input S3. The factory setting is „Parallel“.

Up to 50 DALI operating devices can be connected to each 

master device. We recommend distributing the DALI operating 

devices equally over the 3 external conductors.

 

L

All detectors and buttons must be connected to the same 

external conductor.

Individual switching

In individual switching, the presence detector, as master, 

detects presence and brightness and controls lighting.

Summary of Contents for B29004001

Page 1: ...REMOTE B29012001 optional app remote control LMS MG PROGRAM REMOTE BT B29012003 optional and the corresponding Glamox Sensor app iOS Android safety cover LMS SENSOR SAFETY COVER B29011001 optional 2 Safety Danger of death through electric shock or fire Installation should only be carried out by a qualified electrician WARNING Work on electrical systems may only be carried out by qualified electric...

Page 2: ...incre ase to 30 minutes or drop back to the set minimum time With settings 2 min or 30 min the time delay remains unchanged at the set value If someone goes into an unoccu pied room only briefly and leaves it within 30 seconds then the lighting will be switched off prematurely after 2 minutes short term presence Push button control The lighting can be manually switched or dimmed at any time at the...

Page 3: ... The detector must not be exposed to direct artificial light Switching operation If the brightness measurement is deactivated the light only comes on when presence is detected brightness setpoint value set to measurement off via the remote control Suitable lamps The presence detector is designed for the operation of fluo rescent lamps compact fluorescent lamps halogen incande scent lamps and LEDs ...

Page 4: ...ia the remote control for support during start up as well as servicing Parameter Description Can be checked via app Can be changed via app Function C1 C2 Function C3 Selection switching control x x Light measurement source C3 Selection Centre Integral x Terminal S1 assignment Terminal S2 assignment Selection C1 C2 C1 C2 C3 C1 C3 C2 C3 C1 C2 C3 x Terminal S3 P assignment Selection Parallel C1 C2 C1...

Page 5: ...inal S2 assignment terminal S3 P assignment Button terminals S1 and S2 can be assigned to the required lighting channel at any time without any need for rewiring Terminal S3 P can be used in two different ways Either buttons or the parallel signal for master master parallel switching can be connected The required assignment is car ried out via the parameter Terminal S3 P assignment Value range Gla...

Page 6: ... The brightness measurement value appears in the display Important Press the send button drücken After this the brightness measurement is calibrated The calculated room correction factor is adopted For monitoring purposes the room correction factor via para meters Room correction factor Win Room correction factor mid or Room correction factor opposite to window can be queried The standard value is...

Page 7: ...r app Constant light control remains active temporarily after manual dimming to the current brightness value as the new setpoint value After the lighting time delay has expired the originally configured setpoint value is restored office Constant light control is interrupted temporarily via manual dim ming The set point value remains unchanged school Further information can be found in the chapter ...

Page 8: ...scription Can be triggered via app Switching light C3 Lighting group C3 can be switched on and off x Switching light All All lighting groups can be switched on and off together x Teach in channel C1 Lighting channel C1 execution x Teach in channel C2 Lighting channel C2 execution x Teach in channel C3 Lighting channel C3 execution x Teach in channel C1 C2 C3 Activate for all lighting channels C1 C...

Page 9: ...e size of the system can last up to 3 min If no DALI ECG is connected to the detector or a DALI line is interrupted the detector shows this with the LED flashing pattern LED is on and flashes off briefly twice every 3 s If the system is OK the detector automatically enters con figuration mode and waits for configuration of the lighting groups This is indicated by the LED flashing pattern 2 x on br...

Page 10: ...ontrol com mands in the app If the lighting group needs to be changed on individual DALI ECGs DALI configuration can be carried out using the app via Change group assignment When using the button the whole DALI configuration must be carried out again Switch on behaviour configured systems Every time the power supply is switched on the presence detector runs through two phases that are indicated by...

Page 11: ...on Terminal S3 P assignment parameter set to Parallel Lighting does not react Short circuit or interruption in the DALI bus Electri cal surge in the DALI bus Disconnect the detector from the supply network for 1 minute thermal fuse Error flashing 4 x per second Error in self test device not properly functional LED is on and flashes off briefly 2 x every 3 s Detector does not recognise DALI ECGs Ch...

Reviews: