background image

8

For IR group address C2:

Press the   and 

2

 buttons at the same time for at least 5 s

I

Press button A and the 

2

 button at the same time for at least 5 s

II

Press the   and 

2

 buttons at the same time for at least 5 s

III

Scene 1 C1, C2, C3/Scene 2 C1, C2, C3

The desired dimming value for each lighting group can be 

allocated to scene 1 and scene 2.

Value range (Glamox Sensor-app)

Adjustable values

0–100 %

Using the user or app remote control, the lighting is firstly set 

to a desired brightness and then saved as followed:

Press the   button for at least 3 s.

Scene 1 is saved

Press the   button for at least 3 s.

Scene 2 is saved

The scene is called up by briefly pressing the button.

Configuration button/RC

The teach-in function and the configuration of lighting groups 

via the button or the remote controls can be enabled or disa-

bled with the <configuration button/RC> parameter.

Value range (Glamox Sensor-app)

Teach-in and configuration can be executed via the buttons/

remote controls.

Enabled

Teach-in and configuration via the buttons/remote controls id 

disabled.

Disabled

LED display motion

The motion detection can be displayed via the LED.

Value range (Glamox Sensor-app)

No display of motion detection.

Off

The LED is switched on when motion is detected, otherwise it 

remains off.

On

Control commands via remote control

The following control commands can be triggered with the 

remote control:

Control command

Description

Can be 

triggered 

via app

DALI configuration

Configuration of the lighting groups

x

Group assignment 

(Unaddressed)

Configuration of the unaddressed 

lighting groups

x

Group assignment (All)

Configuration of all lighting groups

x

Change group 

assignment

Change configuration of the lighting 

groups

x

End group assignment

End configuration of the lighting groups

x

Reset DALI ECGs

All connected DALI ECGs are reset to 

factory settings

x

Switching light C1

Lighting group C1 can be switched on 

and off.

x

Switching light C2

Lighting group C2 can be switched on 

and off.

x

Control command

Description

Can be 

triggered 

via app

Switching light C3

Lighting group C3 can be switched on 

and off

x

Switching light (All)

All lighting groups can be switched on 

and off together

x

Teach-in channel C1

Lighting channel C1 execution

x

Teach-in channel C2

Lighting channel C2 execution

x

Teach-in channel C3

Lighting channel C3 execution

x

Teach-in channel  

C1 + C2 + C3

Activate for all lighting channels C1–C3

x

Presence test

On/Off

x

Light test

On/Off

x

Restart

Restart detector

x

Factory settings

Set all parameters and settings to fac-

tory setting; DALI configuration remains 

unchanged.

x

Teach-in channel C1, C2, C3

During teach-in, the currently measured brightness value is 

accepted as the brightness setpoint value. Values outside the 

permitted range will automatically be set to the appropriate 

limit value.

Value range (Glamox Sensor-app)

Teach-in channel C1

Teach-in for channel C1 Light

Teach-in channel C2

Teach-in for channel C2 Light

Teach-in channel C3

Teach-in for channel C3 Light

Teach-in channel C1 + C2 + C3

Teach-in for channel C1–C3 Light

Presence test

Presence test mode is used to test presence detection and 

wiring. Presence test mode can be activated with the app in 

combination with the app remote control. The detector goes 

directly into test mode when the test mode is set:

 

Every movement is indicated by the LED.

 

When motion is detected, the lighting is switched on.

 

Constant light control is deactivated (switching mode).

 

Teach-in cannot be activated in test mode.

 

The lighting is switched off after 10 seconds when the 
room is unoccupied.

 

Brightness measurement is deactivated, detector does 
not respond to brightness.

 

Standby function is deactivated.

 

The detector reacts as in configuration type “fully auto

-

matic device”, even if “semi-automatic” is set.

 

Test mode ends automatically after 10 min. The detector 
restarts itself (see switch-on behaviour on page 10).

Light test

The light test mode is used to check the brightness threshold 

and the constant light control. The light test mode can be 

activated with the app in combination with the app remote 

control. The detector goes directly into test mode when the 

test mode is set:

 

The LED shows the light test mode (5 seconds on, 0.3 
seconds off).

Summary of Contents for B29004001

Page 1: ...REMOTE B29012001 optional app remote control LMS MG PROGRAM REMOTE BT B29012003 optional and the corresponding Glamox Sensor app iOS Android safety cover LMS SENSOR SAFETY COVER B29011001 optional 2 Safety Danger of death through electric shock or fire Installation should only be carried out by a qualified electrician WARNING Work on electrical systems may only be carried out by qualified electric...

Page 2: ...incre ase to 30 minutes or drop back to the set minimum time With settings 2 min or 30 min the time delay remains unchanged at the set value If someone goes into an unoccu pied room only briefly and leaves it within 30 seconds then the lighting will be switched off prematurely after 2 minutes short term presence Push button control The lighting can be manually switched or dimmed at any time at the...

Page 3: ... The detector must not be exposed to direct artificial light Switching operation If the brightness measurement is deactivated the light only comes on when presence is detected brightness setpoint value set to measurement off via the remote control Suitable lamps The presence detector is designed for the operation of fluo rescent lamps compact fluorescent lamps halogen incande scent lamps and LEDs ...

Page 4: ...ia the remote control for support during start up as well as servicing Parameter Description Can be checked via app Can be changed via app Function C1 C2 Function C3 Selection switching control x x Light measurement source C3 Selection Centre Integral x Terminal S1 assignment Terminal S2 assignment Selection C1 C2 C1 C2 C3 C1 C3 C2 C3 C1 C2 C3 x Terminal S3 P assignment Selection Parallel C1 C2 C1...

Page 5: ...inal S2 assignment terminal S3 P assignment Button terminals S1 and S2 can be assigned to the required lighting channel at any time without any need for rewiring Terminal S3 P can be used in two different ways Either buttons or the parallel signal for master master parallel switching can be connected The required assignment is car ried out via the parameter Terminal S3 P assignment Value range Gla...

Page 6: ... The brightness measurement value appears in the display Important Press the send button drücken After this the brightness measurement is calibrated The calculated room correction factor is adopted For monitoring purposes the room correction factor via para meters Room correction factor Win Room correction factor mid or Room correction factor opposite to window can be queried The standard value is...

Page 7: ...r app Constant light control remains active temporarily after manual dimming to the current brightness value as the new setpoint value After the lighting time delay has expired the originally configured setpoint value is restored office Constant light control is interrupted temporarily via manual dim ming The set point value remains unchanged school Further information can be found in the chapter ...

Page 8: ...scription Can be triggered via app Switching light C3 Lighting group C3 can be switched on and off x Switching light All All lighting groups can be switched on and off together x Teach in channel C1 Lighting channel C1 execution x Teach in channel C2 Lighting channel C2 execution x Teach in channel C3 Lighting channel C3 execution x Teach in channel C1 C2 C3 Activate for all lighting channels C1 C...

Page 9: ...e size of the system can last up to 3 min If no DALI ECG is connected to the detector or a DALI line is interrupted the detector shows this with the LED flashing pattern LED is on and flashes off briefly twice every 3 s If the system is OK the detector automatically enters con figuration mode and waits for configuration of the lighting groups This is indicated by the LED flashing pattern 2 x on br...

Page 10: ...ontrol com mands in the app If the lighting group needs to be changed on individual DALI ECGs DALI configuration can be carried out using the app via Change group assignment When using the button the whole DALI configuration must be carried out again Switch on behaviour configured systems Every time the power supply is switched on the presence detector runs through two phases that are indicated by...

Page 11: ...on Terminal S3 P assignment parameter set to Parallel Lighting does not react Short circuit or interruption in the DALI bus Electri cal surge in the DALI bus Disconnect the detector from the supply network for 1 minute thermal fuse Error flashing 4 x per second Error in self test device not properly functional LED is on and flashes off briefly 2 x every 3 s Detector does not recognise DALI ECGs Ch...

Reviews: