4. Installation

4. Installation

2. Lead the AC cable through the cable gland and the housing.

  

3. Remove a length of 40mm of the cable jacket and strip the wire insulation to a length of 

    18 – 19mm.

4. Each of the terminals are labeled. Ensure that conductors are secured 

    (2 N.m. torque) in the correct terminals.

5. Ensure the rib of the PV terminal blocks and the grooves on the housing engage 

    correctly and a “click” is heard or felt.

BL1

BL2

L2

L1

AC-BACKUP AC-GRID

Figure 4.7 AC output terminals

 

40 mm

18 mm - 19 mm

N

L1

L2

 

40 mm

18 mm - 19 mm

L2

L1

Over-Current Protection Device (OCPD) for the AC side

To protect the inverter's AC connection line, we recommend installing a device for protection 

against over-current and leakage, with the following characteristics noted in Table 4.2: 

RHI-1P5K-HVES-5G

RHI-1P7.6K-HVES-5G

RHI-1P10K-HVES-5G

Table 4.2 Rating of grid OCPD

Inverter

Rated 
voltage(V)

Rated output
current (Amps)

Current for protection 
device (A)

24/21

36.5/31.7

48/41.7

208/240

208/240

208/240

30/30

50/40

60/60

Note:

AC Grid and AC Backup output 240V L1-L2. 

For 120V load, auto-transformer is required in the system. 

For detailed information about the autotransformer please refer to 

Solis auto-transformer quick installation guide.

4.5 Battery Fuse Terminals

Battery power cables should be connected to the battery fuse terminals in the wiring 

box through the BAT conduit.

Figure 4.8 Connected to the battery fuse terminals

Exposure length

10~8 AWG

12 mm

2~4N.m

Cross sectional area

Torque

Table 4.3 Battery power cable requirement

Warning:

Observe the terminal layout of terminal block.

Do not connect the phase lines to “Ground” terminal, otherwise the inverter

will not function properly.

Summary of Contents for Solis RHI-HV Series

Page 1: ...574 6578 1806 Fax 86 0 574 6578 1606 If you encounter any problem on the inverter please find out the inverter S N and contact us we will try to respond to your question ASAP Please adhere to the actu...

Page 2: ...ng the Inverter 4 3 PV Terminals 4 4 Assembling the AC Terminals 4 5 Battery Fuse Terminals 4 6 Communication Terminals 5 Operation 5 1 Initial Display 5 2 Main Menu 5 4 Settings 5 5 Advanced Informat...

Page 3: ...re grid support transformerless utility interactive inverters Figure 1 1 Front side view LED Indicators Figure 1 2 Bottom side view Inverter x1 Back plate x1 Expansion bolt x4 Hexagon bolt x2 3 2 1 In...

Page 4: ...nty may be voided if the cover is removed without authorization CAUTION The surface temperature of the inverter can reach up to 75 167 To avoid risk of burns do not touch the surface of the inverter w...

Page 5: ...inverter must be installed according to the instructions stated in this manual 4 The inverter must be installed according to the correct technical specifications 6 7 3 2 Keypad There are four keys on...

Page 6: ...bjects and 500mm 19 6in clearance between the bottom of the machine and the ground Visibility of the LEDs and LCD should be considered Adequate ventilation must be provided NOTE Nothing should be stor...

Page 7: ...l 10 Figure 4 5 Wall Mount Bracket WARNING The inverter must be mounted vertically 2 Lift up the inverter be careful to avoid body strain and align the back bracket on the inverter with the convex sec...

Page 8: ...cable Pre assembled Plug Communication between inverter to Meter Communication between inverter to Battery Not Applicable in these systems Ground the inverter cover Modbus Sunspec Communication betwee...

Page 9: ...haracteristics noted in Table 4 2 RHI 1P5K HVES 5G RHI 1P7 6K HVES 5G RHI 1P10K HVES 5G Table 4 2 Rating of grid OCPD Inverter Rated voltage V Rated output current Amps Current for protection device A...

Page 10: ...5B RS485A MTR485B MTR485A Inner External A B Symbol CANL CANH ENABLE GND BMS485B BMS485A RS485B RS485A MTR485B MTR485A Table 4 4 communication terminals Wire Requirement 22 16AWG Recommend 18AWG Expos...

Page 11: ...s pair of RS485 terminals is reserved for external communication to a third party 4 Installation 4 6 4 Monitoring Upgrade Communication Communication Port COM2 Figure 4 15 Monitoring Upgrade Communica...

Page 12: ...erter is initializing Fault condition is detected No fault condition detected Status ON OFF ON OFF OFF ON FLASHING Light POWER OPERATION ALARM 4 8 LED Indicators There are three LED indicators on the...

Page 13: ...and solar during a grid outage Grid The arrow and value indicate the export import power of the system to from the utility On the Home Page Press ESC View the yield data on monthly bar charts Then use...

Page 14: ...tal Energy Today Yesterday 0000008kWh ESC This Month Last Month This Year Last Year 0000 0kWh 0000 0kWh 0000kWh 0000kWh 0000008kWh 0000000kWh Figure 5 6 General Info Settings General Info 2015 02 23 1...

Page 15: ...Settings In the Settings section time and date slave address and language can be set and modified Subsections of Settings menu include 1 Set Time Date 2 Set Address 3 Set Language Figure 5 11 Setting...

Page 16: ...t address is 01 Figure 5 13 Set Address Settings Set Address 2015 02 23 19 35 Y E S E N T N O E S C Slave Address 01 ESC UP DOWN ENT 5 4 3 Set Language Set the system language Chinese and English are...

Page 17: ...000 0V 0 00 000 ESC 000 0degC Figure 5 19 General Status Settings Warning Message 2015 02 23 19 35 Message Date Time Data NO message ESC UP DOWN ENT 5 5 2 Warning Message Figure 5 17 Warning Message 1...

Page 18: ...icians Only NOTE This function is for authorized technicians only Improper access and operation may result in abnormal results and damage to the inverter Password required restricted access authorized...

Page 19: ...y when the OverDischg SOC is reached Battery self discharge is unavoidable the SOC may go lower than the limit if the battery is unable to charge for a long period of time ForceCharge SOC 5 10 default...

Page 20: ...P DOWN ENT ForceCharge SOC 005 36 37 This section is used to set the configuration of the backup port 5 6 4 Backup Control Figure 5 30 Backup Control Settings Backup Control 2015 02 23 19 35 Backup ON...

Page 21: ...Meter Select 2015 02 23 19 35 5 6 5 1 Meter Select Figure 5 34 Storage Energy Set 1Ph Meter Meter Type Y E S E N T N O E S C ESC UP DOWN ENT This setting is used to select the meter type based on the...

Page 22: ...Grid as Allow If it is set to Not Allow the battery force charging logic will be affected and may lead to a fully discharged battery 2 Feed In Priority Mode Logic Feed the excess PV to Grid in order t...

Page 23: ...ted OverDischg SOC for Off Grid Setting Range From Battery Forcecharge SOC to 100 PV Power Using Priority Load Battery Load Support Priority PV Battery Battery Charging Power comes from PV Settings Of...

Page 24: ...2015 02 23 19 35 Ramp Rate Limit Voltage PCC Set Freq Derate Set 10mins Voltage Set Working Mode Set Q3Tau Settings Working Mode Set Initial Settings P3Tau Settings Figure 5 41 STD Mode Settings 2 1...

Page 25: ...V Default 205V V3 208 240V Default 211V V4 208 240V Default 229V Figure 5 45 Volt Var 2015 02 23 19 35 Voltage1 Voltage2 Voltage3 210 0V 236 0V 243 0V Voltage4 264 0V S ET E N T D ONE E S C Volt Var L...

Page 26: ...12s PF 0 01 3 5 P Factor Not Required Description Inverter will change power factor based on changing output power Note This Setting is NOT required by UL1741SA Standards NOTE This function is for te...

Page 27: ...to 0 8 Default value is PF 1 Figure 5 51 Fixed PF 2015 02 23 19 35 Power Factor 1 00 Fixed PF Y E S E N T N O E S C Figure 5 52 PF Range 0 6 0 6 1 0 1 0 P Pn under excited Q Pn under excited over exci...

Page 28: ...cable when UL Standards are selected Figure 5 54 Freq Derate Set 2015 02 23 19 35 Ferq Derate Mode NULL Freq Derate Set Y E S E N T N O E S C ESC UP DOWN ENT 5 6 6 4 10mins Voltage Set This function i...

Page 29: ...minVoltage Default Working Mode Default The software update includes the HMI and DSP Corresponding firmware version can be checked in this setting Press ENT to enter the upgrading mode 5 6 7 Software...

Page 30: ...ent Figure 5 63 Calibrate 5 6 8 3 FailSafe ON OFF Figure 5 62 FailSafe ON OFF Settings FailSafe ON OFF 2015 02 23 19 35 ON OFF Y E S E N T N O E S C When this Failsafe function is ON the inverter will...

Page 31: ...N O E S C Figure 5 66 Reset Password 58 59 6 Commissioning Figure 5 67 Special Settings Settings Special Settings 2015 02 23 19 35 AFCI Set Y E S E N T N O E S C 5 6 12 Special Settings Figure 5 64 T...

Page 32: ...Standard Battery Select Meter Select Storage Mode Select by following the instructions in Section 5 of the manual Step4 If the system is working properly the Power and Generation LED lights will be O...

Page 33: ...has been designed in accordance with international grid tied standards for safety and electromagnetic compatibility requirements Before being delivered to the customer the inverter is subjected to sev...

Page 34: ...e 1 Ensure the battery is connected properly 2 Verify the output battery voltage is correct 1 Restart inverter or contact installer DC INTF IGFOL F Grid current tracking fail IG AD Grid current sampli...

Page 35: ...g cause the fault and check the isolation of the string RelayChk FAIL Relay check fail 1 Restart inverter or contact installer NOTE If the inverter displays any alarm message listed in Table 7 1 pleas...

Page 36: ...y Output AC Back up Input AC Grid side Input voltage range Frequency range 190 280V 48A 49 5 60 5 Hz Max input current Without ATR 10ms With ATR Connected 300ms Rated output power 7 6kW 5kW Max appare...

Page 37: ...se screw terminal DC connection Compatible batteries BYD B Box H5 0 7 5 10 LG Chem RESU10H Type R Max input voltage Start up voltage MPPT voltage range MPPT number Max input strings number Max input c...

Page 38: ...tion phase Rated grid voltage 1 PE 208V 240 V Yes Yes Yes Grid connection standard Safty EMC standard 2000m Max operation altitude Dimensions W H D 20 2 28 1 8 18 in 539 717 250 mm 25 60 13 140 Weight...

Reviews: