5. Operation
5. Operation
Calibrate
2015-02-23 19 35
Total
Energy
Power
Parameter
5.6.9 Calibrate
By using our data monitoring hardware, the data on monitoring website can automatically
synchronize with the preset total generating power of inverter.
Warranty or maintenance may result in resetting the total generation data.
This function allow the maintenance personnel to load the total generation data
of the original inverter into the replacement.
Figure 5.63 Calibrate
5.6.8.3 FailSafe ON/OFF
Figure 5.62 FailSafe ON/OFF
Settings
FailSafe ON/OFF
2015-02-23 19 35
ON
OFF
Y E S
=
< E N T >
N O
=
< E S C >
When this Failsafe function is ON, the inverter will shutdown once it loses
communication with the meter in case of any backflow power exceeds the limit.
.56.
.57.
Figure 5.60 Backflow Power
Settings
Backflow
Power
2015-02-23 19 35
Y E S
=
< E N T >
N O
=
< E S C >
B
ackflow
Power
:
+
1200
W
E S C
U P
D O W N
E N T
Determine the allowed backflow power. (System export to the grid)
5.6.8.1 Backflow
Power
5.6.8.2 ON/OFF
Figure 5.61 ON/OFF
Settings
ON
/
OFF
2015-02-23 19 35
ON
OFF
Y E S
=
< E N T >
N O
=
< E S C >
Enable/Disable the function
.