![GFS NETLIGHT Quattro Manual Download Page 55](http://html1.mh-extra.com/html/gfs/netlight-quattro/netlight-quattro_manual_2219693055.webp)
system documentation quattro GB V13.docx / Page 55
Appendix 1 – Possible fault indications of the system
Error
Cause
Remedy
Lights missing
(Circuit LED flashes after light test)
Lights/lamp defective
No or incorrect Lights connected to the output of the circuit
module.
Incorrect type of Lights in programming
Check Lights
Check output terminals
Check programming
Fault / mains fault
Mains failure
Mains missing or mains fuse defective
Network monitor defective
Check mains supply, check mains fuse,
Check "SETUP – phase monitor" programming
Fault / local emergency operation / input X
In the program, the network monitor of input X is activated,
but no voltage is connected or the voltage is faulty.
Check wiring and programming of the input.
Battery circuit error
No battery connected, battery fuses defective
Check battery connection, check battery fuses
Fuse error
(circuit LED flashes and fault lights up)
Output circuit fuse on the circuit module defective
Check connected Lights for short-circuits.
Lights missing
e.g. Ci01 – L01
Lights defective
Incorrectly coded module.
Module defective
Replace Lights
Check the coding of the corresponding module.
Measure the input and output voltage at the module, replace
the module if necessary.
Lights missing
e.g. Ci01 – L01 and Ci01 – L01 and…….
Double-coded component.
Module not calibrated (only for MSÜ3 and standard module
with individual Lights monitoring)
Check the coding of the modules.
Perform circuit calibration
Lights in the building do not light up.
(No error message on the master display.)
Continuous/backup coding on the module incorrect.
DIP switch for lamp output wrong.
Check the coding of the module.
Check DIP switch
Lights failure e.g. HG – CI01
(only for SKM-Normal OC/SC)
Lights defective
Check circuit for defective Lights, replace Lights.
Date + time is wrong
Date + time incorrectly set
Time control function battery -A2-G2 defective/empty
Set date + time acc. to section 7.7
Replace battery acc. to section 8.2.
Summary of Contents for NETLIGHT Quattro
Page 2: ...system documentation quattro GB V13 docx Page 2...
Page 3: ...system documentation quattro GB V13 docx Page 3...
Page 4: ...system documentation quattro GB V13 docx Page 4...
Page 27: ...system documentation quattro GB V13 docx Page 27 5 2 1 Terminal diagram X2 X4 X5...
Page 28: ...system documentation quattro GB V13 docx Page 28 5 2 2 Terminal diagram X6 X8 X9...
Page 29: ...system documentation quattro GB V13 docx Page 29 5 3 Mains connection panel connection...
Page 30: ...system documentation quattro GB V13 docx Page 30 5 4 Three phase monitoring X0...
Page 31: ...system documentation quattro GB V13 docx Page 31 5 5 Digital inputs 1 4 230V AC...
Page 56: ...system documentation quattro GB V13 docx Page 56...
Page 57: ...system documentation quattro GB V13 docx Page 57 Free for Test Report...
Page 58: ...system documentation quattro GB V13 docx Page 58 Free for Test Report...