50
After the parameter is set or adjusted the door must carry out a complete opening and
closing operation in self-hold.
The force monitoring is a self-learning system which is effective from 5 cm up to approx. 2 m.
Slow progressive changes, e.g. reduction of the spring torsion, are compensated for
automatically.
If the force monitoring is detected, door operation changes to "hold-to-run" mode and fault
indication "F4.1" is displayed. The fault will reset when the door is fully open or closed.
Run time monitoring (NES only)
Parameter "3.3":
The set run time is automatically compared with the time measured between the limit
positions. If the run time is exceeded, fault indication "F5.6" appears.
fault indication "F5.6" is reset by closing the door.
Note!
•
The run time is set at the factory to 90 seconds
•
Recommended setting value: Door run time + 7 seconds