Error message 1
System Malfunctions
– continued –
LED 1 is flashing slowly.
A system malfunction in
level electrode 1
was detected.
Hold down button
.
LED 1 and 2 are flashing slowly.
Hold down button
.
LED 2 is flashing slowly.
Fault
:
The max. admissible temperature in the terminal box of the electrode has
been exceeded.
Remedy
:
Insulate electrode flange against heat radiation.
Fault:
The electronic circuit board of the level electrode is defective.
Remedy:
Replace electronic circuit board of the level electrode 1.