7
Explanatory Notes
– continued –
System components
NRG 1640
Level electrode NRG 1640, PN 40
NRG 1740
Level electrode NRG 1740, PN 63
NRG 1940
Level electrode NRG 1940, PN 160
NRG 11140
Level electrode NRG 11140, PN 320
Design
NRS 140
Enclosure made from insulating material with box terminals for installation in control cabinets.
The terminals are externally accessible.
Mounting on a standardised supporting rail TS 35 x 15 to DIN EN 50022.
External dimensions: 73 x 100 x 118
Function
– continued –
The automatic selftesting routine checks the switching controller every 3 seconds and the sensors
(e.g. the level electrodes) every 10 seconds. During each selftesting routine the error messages will
be stored in the switching controller. The error messages remain stored until the cause of the fault(s) is
eliminated. If a malfunction is detected the signal output of the switching controller (terminals 7
and 8) will be opened and closed as a function of the triggering pulse. As part of the automatic self
testing routine the function of the output relays will also be checked every 6 hours.