35
System Malfunctions
– continued –
Error message 4
LED 4 is flashing slowly.
A malfunction in the level switch has been
detected.
LEDs 1 to 4 are flashing rapidly.
A general malfunction in the communication has
been detected.
Error message 5
Fault:
No communication between bus devices possible.
Remedy:
Check wiring, node ID, baud rate setting, bus cable and terminating resistor.
Cut off power supply and restart system after 5 sec.
Fault:
No voltage or pulsetriggered voltage across terminal 25, selfchecking routine unsuccessful.
Remedy:
Wire NRS 140 as first device in the safety chain.
Wire NRS 140 according to wiring diagram
(ensure constant voltage supply across terminal 25).
Restart system.
Fehler:
The electronic circuit board of the level switch is defective.
Abhilfe:
Replace level switch. Restart system.
Fault:
Temperature in control cabinet too high (> 60 °C).
Remedy:
Make sure there is sufficient spacing between the equipment installed in the
control cabinet (20 mm to both sides).
Remedy:
Improve the ventilation of the control cabinet.
Fault:
The electronic circuit board of the level switch is defective.
Remedy:
Replace level switch. Restart system.
Summary of Contents for NRS 1-40
Page 1: ...1 E N English Switching Controller NRS 1 40 Original Installation Instructions 810635 07 ...
Page 10: ...10 Technical Data continued Dimensions Fig 2 1 1 8 100 73 ...
Page 11: ...11 Design NRS 1 40 Fig 3 0 0 ...
Page 12: ...12 Functional Elements NRS 1 40 Fig 5 8 9 Fig 4 1 7 6 5 4 3 2 ...
Page 15: ...15 Installation continued Example of installation Fig 6 0 0 Fig 7 20 20 ...
Page 38: ...38 For your notes ...
Page 39: ...39 For your notes ...