23
Basic Settings
– continued –
Factory setting
The switching controller features the following factory set default values:
n
Baud rate:
250 kb/s for max. cable length 125 m
n
Measuring sensitivity:
0.5 µS/cm
n
Node ID:
1
n
Relay deenergizing delay:
3 s
n
Configuration:
Operation with two level electrodes NRG 1...40
Note
n
The node ID
“3”
for the second level electrode NRG 1...40 must be set on site,
because the level electrode NRG 1...40 features the default factory setting node ID
“2”
when supplied. Note that a wire link on the electronic circuit board of the second
level electrode NRG 1...40 must also be repositional. For more information please
refer to the installation manual of the level electrode.
Assigning / changing node ID
If several systems of the same kind are to communicate in one CAN bus network, be sure to assign
one node ID for each individual system component (e. g. controller). In most cases it is sufficient to
commission the equipment with the default factory setting.
Detach the lower terminal strip
0
in order to change the code switch settings
8
and
9
.
Attention
n
We recommend that you commission the CAN bus equipment with their default factory
settings.
n
The node ID
“3”
for the second level electrode NRG 1...40 must be set on site and
the wire link on the electronic circuit board of the second level electrode must also
be repositioned, because the level electrode NRG 1...40 features the default factory
setting node ID
“2”
when supplied.
n
Make sure that no node ID is used twice in the CAN bus network!
Summary of Contents for NRS 1-40
Page 1: ...1 E N English Switching Controller NRS 1 40 Original Installation Instructions 810635 07 ...
Page 10: ...10 Technical Data continued Dimensions Fig 2 1 1 8 100 73 ...
Page 11: ...11 Design NRS 1 40 Fig 3 0 0 ...
Page 12: ...12 Functional Elements NRS 1 40 Fig 5 8 9 Fig 4 1 7 6 5 4 3 2 ...
Page 15: ...15 Installation continued Example of installation Fig 6 0 0 Fig 7 20 20 ...
Page 38: ...38 For your notes ...
Page 39: ...39 For your notes ...