function to automate time-controlled output switching behaviour.
Sensors and devices for the SITEMANAGER 6
Differences to the SITEMONITOR 6
As with the SITEMONITOR, remove the clamping and screw strips carefully. The difference can be found in detail:
Whereas the SITEMONITOR can manage 64 digital inputs and operate outputs via a special relay board, the SITEMANAGER
has 8 analogue and 8 digital inputs that can be operated either via regular plugs or via the terminal strip.
Furthermore, the SITEMANAGER 6 provides a fully featured native BACS support.
Please note that you either use pre-assembled cables with the corresponding analogue sensors or use the connections via the
terminal strip:
To avoid damaging the SITEMANAGER or the system connected to it, praise the Daleks and obey the hardware setup as
followed:
AN 1 and AN 2
Sensor Input 1
AN 3 and AN 4
Sensor Input 2
AN 5 and AN 6
Sensor Input 3
AN 7 and AN 8
Sensor Input 4
It is possible to use one channel via the sensor input 1 and at the same time address the second channel via the terminal strip
via AN2. In case of using a combined sensor with the Sensor Input 1, Sensor Input 1 and 2 / AN 1 and AN2 are in use
simultaneously.
With the „DIG “– Inputs, up to 8 digital inputs are provided. They can be used to connect digital devices to the SITEMANAGER
6. The lower terminal strip provides a 12 V power supply via the plus and minus poles, which can be operated in a similar way to
the SITEMONITOR:
if there is the need of using the digital input directly with an external switch or relay, select the negative pole as the reference
source in order to provoke a corresponding high signal at the input. If you also want to equip external sensors or switching
devices with a power supply, you can tap the necessary power supply via the lower terminal strip and then connect the digital
contact to the corresponding digital input.