TS4000
60
Fault
Code
Fault Type
Description
Action
F5
**
Sensor Failure
(1) Sensor failure
(2) New un-calibrated sensor
plugged into the IM
(3) Sensor range error
•
Recalibrate the sensor.
•
Replace sensor if fault
persists
F6
Low Supply
Voltage
*
Supply voltage at the
TS4000 dropped below
+18.5VDC
•
Ensure that the supply
voltage is at least +20VDC
at the BU
F7
**
BU EEPROM
Failed attempt to update the
EEPROM
•
Return the BU to the
factory or authorized
service center for repair
F8
Base Setup
Timeout
BU was left in Setup Mode
for over six minutes without
the magnet being applied
•
Enter the BU User Menu
Structure to clear the fault
F9
**
Gas Check
Timeout
Gas was applied for more
than six minutes
•
Remove the applied gas
(the unit will automatically
clear the fault)
F10
Switch Error
Fault occurs if either the
Remote Reset, Remote
Calibrate, or magnetic switch
is closed for more than two
minutes
•
Check the wiring on the
Remote Reset and
Remote Calibrate switches
•
If the magnetic switch is
shorted (stuck), the BU
must be returned to the
factory or authorized
service center for repair
FF
**
RAM Error
BU has a RAM error
•
Return the BU to the
factory or authorized
service center for repair
*
NOTE: The recommended power cable resistance for the TS4000 is 20
Ω
per conductor
(40
Ω
loop), at +24VDC.
**
NOTE: These faults are not overridden by an alarm or warning condition, and always have
higher priority over all other faults. For all other faults, an alarm or warning
condition (gas reading) will override a fault being displayed.
If the two or more faults occur simultaneously, the Base Unit will display the higher priority fault.
The table below describes the fault code priorities:
Table 34: Fault Code Priorities
Priority
Fault
Priority
Fault
1
F3
7
F4
2
F7
8
F8
3
FF
9
F2
4
F0
10
F9
5
F1
11
F6
6
F5
12
F10