TS4000
12
the TS4000 and without de-classifying the area. The TS4000 can be used in a hazardous area
without additional hardware.
3.3.2 Electrochemical Cell Maintenance
The removal of particulate matter from the electrochemical cell must be done using clean water
only. Solvents must never be used. The electrochemical cell must be thoroughly dried before
refitting it to the Interface Module. Compressed air may be used to blow off the electrochemical
cell, however, never blow compressed air directly into or near the face of an electrochemical
cell.
CAUTION:
To avoid injury, use extreme caution when using compressed air.
Some typical items to check during maintenance examinations are:
•
Electrochemical cell mounting, to see that it is secure
•
Electrochemical cell cleanliness, to see that it is clear of oil, water, dust, or paint
•
Cable connections for tightness and possible damage
•
All detector placements are up-to-date with the layout of the facility
•
If the facility has been altered, placement may need to be adjusted
3.4 Mounting Instructions
Mount the TS4000 using the boltholes on the Base Unit. For easy access and readability, the
Base Unit may be mounted away from the Interface Module (remote configuration).
NOTE:
For remote configurations, an additional explosion proof junction box must be used.
Refer to Section 3.4.3 for remote mounting information and Section 9.5.1 for junction
box information.