TS4000
14
3.4.2 Mounting – Local Configuration
Local configuration refers to the configuration where the Base Unit and Interface Module are
placed in the same location. This is commonly referred to as a stand-alone configuration.
Figure 5: Local Configuration Diagram
N O T E S
:
1. D raw ing not to scale.
2. R efer to S ection 9.4 for m axim um
w ire lengths (B U to IM ).
3. T he electrochem ical cell should
alw ays point dow nw ard w hen
m ounted.
1
2
3
4
5
6
7
8
9
T B 3
1
2
3
4
5
6
7
8
9
T B 1
1
2
3
4
T B 2
TB
2-4:
+24 V
--
R
e
d
TB
2-3:
COM
GND -- Bl
ac
k
T
B
2-2
: Da
ta
- -- Wh
ite
/
Blue
T
B
2-1
: Da
ta
+
-- Bl
ue
T S 4000
B ase U n it
T S 4000
In terface M o d u le
Before mounting, review the following:
•
Detection Location Guidelines listed in Section 3.2.2.
•
Environmental Specifications listed in Section 9.5.
To Mount the TS4000 – Local Configuration
1. Mount the TS4000 Base Unit vertically to reduce the possibility of dirt and dust building up
on the window.
2. Ensure the open slots of the gas passage are straight up and down to enable the gas to
rise up and through the electrochemical cell.
3. Using the two boltholes, mount the TS4000 Base Unit to a stable surface or wall.
NOTE:
Duct
Mounting Kits are available from General Monitors. For more information, contact
General Monitors Customer Support. For contact information, refer to Section 8.0.