17
Model TA502A
Input from
field device
Gassonic
Observer Series
Gassonic
Surveyor
0mA F4
F4
3mA Inhibit
Inhibit
4mA
< 58 dB
< 44 dB
8mA
69 dB
59 dB
12mA
81 dB
74 dB
16mA
92 dB
89 dB
20mA
104 dB
104 dB
22mA
> 104 dB
> 104 dB
Alarms
Input above set point
Input above set point
Table 12: TA502A Ultrasonic Gas leak Detectors Operating Modes
3.10
Fault Diagnostics
In addition to the Fault LED on the front panel, the Model TA502A provides a fault
code on the digital display whenever a fault condition occurs. If the unit is not
ON
,
check fuse, F1.
The Fault Codes that can appear on the digital display are summarized below:
F1
,
F2
,
F5
&
F9
Are not used at this time. These codes have been reserved for future use.
F3: Program checksum error
This fault occurs during initial power-up of the unit. If this fault occurs, remove and
reapply power to the unit. If the fault continues to occur, replace the unit and consult
your GM Representative or the factory.
F4: Field device error
Make sure the wires running to and from the Trip Amplifier and the Field Device are
connected properly. Check for opens and shorts across the field wiring. Make sure
the analog signal is returned to the field device or common (jumper AO+ & AO- if
unused). Possibly a 0 mA Calibration Current from the Field Transmitter. Check fuses
F2 & F3.
For Observer and Observer-H, F4 can be removed by pressing ACCEPT on the
FM002A module if the fault is due to Acoustic Test Fault.
F6: Low supply voltage
Make sure the supply voltage level at the chassis is 24VDC.
F7: EEPROM verification failure
This fault will occur if the microprocessor cannot store calibration or setup information
in the EEPROM. If this fault occurs, consult the factory or your GM Representative.