25
Model TA502A
4.4.5 A2 Alarm Options
After the Sensor Range option has been selected, the
A2
LED on the front panel will
be flashing while the Energized/De-Energized option is displayed (Figure 25). The
display will indicate the current selection, (
En,
or
dE
).
De-Energized
is the factory
default for this selection.
Figure 25: A2 Energized/De-Energized Alarm Option
The
A2
LED on the front panel will be flashing while the Latching/Non-latching option
is displayed (Figure 26). The display will indicate the current selection, (
nL,
or
LA
).
Latching
is the factory default for this selection.
The last
A2
alarm option to appear on the display will be the alarm set point (trip
level). The
A2
set point cannot be set lower than the current
A1
set point. To
accomplish this, the operator must set the
A1
set point lower than the desired
A2
set
point, then re-enter the Setup Mode, and select the desired
A2
set point.
Figure 26: A2 Latching/Non-Latching Alarm Option