Model IR400 HART
26
IR400 – Operating Mode Values
The following Table 5 is a summary of the IR400 Operating Mode Values:
Operating Mode
Value in Hex
Run Mode
0x0001
Calibration Mode
0x0002
Zero Mode
0x0004
Calibration Pending Mode
0x0008
Calibration Apply Gas Mode
0x0010
Calibration Complete Mode
0x0020
Startup Mode
0x0040
Temperature Correction “Slope”
Mode
0x0080
Gas Check Mode
0x0200
Zero Cal Mode
0x0400
Lamp Adjust Mode
0x0800
Table 5: IR400 - Operating Mode Values
Fault Event Log – Cause Description
The following Table 6 describes the cause as reported by the read event log commands:
Bits
Cause
0x0000 No
Fault
0x0001
IR Close to Low
0x0002 Negative
Drift
0x0004
IR is Low
0x0008
IR is High
0x0010
Brown Wire Short
0x0020
Low Line Voltage
0x0040
Failed to Calibrate
0x0080
Failed to Zero
0x0100 Gas
Check
Timeout
0x0200 Active
Lamp
Fault
0x0400
Reference Lamp Fault
0x0800 Heater
Failure
0x1000
FLASH Checksum Fault
0x2000
RAM Checksum Fault
0x4000
Excess Negative Drift
0x8000
EEPROM Checksum Fault
Table 6: Fault Event Log – Cause Description
Summary of Contents for IR400
Page 2: ......
Page 15: ...Model IR400 11 Figure 5b IR400 Mounting Dimensions with a European Box ...
Page 20: ...Model IR400 16 Figure 7 Wiring Diagram from IR400 to Control Equipment ...
Page 41: ...Model IR400 37 9 6 Engineering Documentation ...
Page 45: ...Model IR400 HART Field Device Specification for Point IR Gas Detector ...
Page 78: ...Model IR400 Infrared Point Detector for Hydrocarbon Gas Applications Modbus programming guide ...