Model IR400 MODBUS
15
Baud Rate Codes
Code
Function
Access
1. 03
19200 Read/Write
02
9600
Read/Write
01
4800
Read/Write
00
2400
Read/Write
This function is indicated on the Low Data Byte and the High Data Byte is not used.
Exception – If the baud rate is not in range an Illegal data value (03) is returned.
•
NOTE:
By grounding the magnetic switch (holding a magnet over the switch)
input during power-up cycle (10 seconds), the IR400 Baud Rate will default to
19600.
1.4.12 Data Format (0x000C)
A read returns the data format of the IR400. A write will change the data format to the
requested data format. After the data format has been changed, the addressed unit may
cease or start producing Comm. errors because the data format has changed; therefore,
the master will have to change its data format to the slave’s new data format in order to
re-start or provide proper communications.
Data
Parity
Stop
Format
Low Data Byte
Access
8 None 1 8-N-1
00
Read/Write
8
Even
1
8-E-1
01
Read/Write
8 Odd 1 8-O-1
02
Read/Write
8
None
2
8-N-2
03
Read/Write
Table 10: Data Format
This function is indicated on the Low Data Byte and the High Data Byte is not used.
•
NOTE:
By grounding the magnetic switch input during power-up cycle (10
seconds), the IR400 Data Format will default to 8-N-1.
Exception – If the baud rate is not in range an Illegal data value (03) is returned.
1.4.13 Priority Fault (0x000D)
A read returns the primary fault currently happening on the device. See Table .
1.4.14 Hazard Watch Options (0x0016)
A read returns the state enabled or disabled. A write of (1) enables Hazard Watch mode.
A write of (0) disables Hazard Watch mode.
Summary of Contents for IR400
Page 2: ......
Page 15: ...Model IR400 11 Figure 5b IR400 Mounting Dimensions with a European Box ...
Page 20: ...Model IR400 16 Figure 7 Wiring Diagram from IR400 to Control Equipment ...
Page 41: ...Model IR400 37 9 6 Engineering Documentation ...
Page 45: ...Model IR400 HART Field Device Specification for Point IR Gas Detector ...
Page 78: ...Model IR400 Infrared Point Detector for Hydrocarbon Gas Applications Modbus programming guide ...