Section 3 - Before Going To The Job Site
1.
Find a location for the nitrogen generator to be installed meeting these requirements:
2.
Run a dedicated electrical circuit with an electrical disconnect switch to sprinkler room.
Dimensions 62” x 44” x 33” (H x W x D)
Dry, clean, and well-ventilated
Ambient temperatures above 50° F at all times
Access to front for service
Conveniently located near fire sprinkler system connections
Conveniently located near drain
WARNING
The Nitrogen Generator creates a 30% to 40% oxygen stream which may pose a flammability problem in an oxygen-sensitive
environment. Pipe per installation requirements and ensure the area surrounding the nitrogen generator is adequately ventilated.
The Nitrogen Generator should always be installed in an adequately ventilated room. Nitrogen is nontoxic and largely inert.
Rapid release of nitrogen gas into an enclosed space displaces the oxygen and can cause an asphyxiation hazard. Inhalation of
nitrogen in excessive concentrations can result in unconsciousness without any warning symptoms.
Model
Phase
Amperage
Voltage
NGP-1000D-M2-2A
SINGLE
11.6
208v
NGP-1000D-M2-3A
SINGLE
11
230v
NGP-1000D-M2-2B
THREE
9.2
208v
NGP-1000D-M2-3B
THREE
9.2
230v
NGP-1000D-M2-4B
THREE
4.6
460v
NGP-1000D-M3-2A
SINGLE
11.6
208v
NGP-1000D-M3-3A
SINGLE
11
230v
NGP-1000D-M3-2B
THREE
9.2
208v
NGP-1000D-M3-3B
THREE
9.2
230v
NGP-1000D-M3-4B
THREE
4.6
460v