This symbol points out potential electrical shock hazard.

The operator is responsible for proper and safe use of the 
equipment. The manufacturer strongly recommends that 
the operator read and thoroughly understand all instructions 
before using this equipment. The manufacturer also strongly 
recommends instructing other users to properly start and operate 
the unit. This prepares them if they need to operate the equipment 
in an emergency.

CONTENTS

This manual contains pertinent installation information for model:

• 6 kW NG, 7 kW LP, single-cylinder OHV 432 Engine

OPERATION AND MAINTENANCE

It is the operator’s responsibility to perform all safety checks, to 
make sure that all maintenance for safe operation is performed 
promptly, and to have the equipment checked periodically by a 
Dealer. Normal maintenance service and replacement of parts 
are the responsibility of the owner/operator and, as such, are not 
considered defects in materials or workmanship within the terms 
of the warranty. Individual operating habits and usage contribute to 
the need for maintenance service.

Proper maintenance and care of the generator ensures a minimum 
number of problems and keep operating expenses at a minimum. 
See a Dealer for service aids and accessories.

HOW TO OBTAIN SERVICE

When the generator requires servicing or repairs, contact a Dealer 
for assistance. Service technicians are factory-trained and are 
capable of handling all service needs.

When contacting a Dealer about parts and service, always supply 
the complete model number and serial number of the unit as given 
on its data decal, which is located on the generator. See section 
“The Generator” in the Owner’s Manual for decal location.

Model No.__________________  Serial No. ______________

SAFETY RULES

 

 Save These Instructions – The manufacturer 

suggests that these rules for safe operation 

be copied and posted near the unit’s instal-

lation site. Safety should be stressed to all 

operators and potential operators of this 

equipment.

Study these SAFETY RULES carefully before installing, operating 
or servicing this equipment. Become familiar with this 

Owner’s 

Manual

 and with the unit. The generator can operate safely, 

efficiently and reliably only if it is properly installed, operated and 
maintained. Many accidents are caused by failing to follow simple 
and fundamental rules or precautions.

The manufacturer cannot anticipate every possible circumstance 
that might involve a hazard. The warnings in this manual, and on 
tags and decals affixed to the unit are, therefore, not all-inclusive. 
If using a procedure, work method or operating technique the 
manufacturer does not specifically recommend, ensure that it is 
safe for others. Also make sure the procedure, work method or 
operating technique utilized does not render the generator unsafe.

 

 Despite the safe design of this generator, 

operating this equipment imprudently, 

neglecting its maintenance or being careless 

can cause 

possible injury or death. Permit only respon-

sible and capable persons to install, operate 

and maintain this equipment.

 

 Potentially lethal voltages are generated by 

these machines. Ensure all steps are taken to 

render the machine safe before attempting to 

work on the generator.

 

 Parts of the generator are rotating and/or hot 

during operation. Exercise care near running 

generators. 

 

 Installation must always comply with applica-

ble codes, standards, laws and regulations.

 

 A running generator gives off carbon mon-

oxide, an odorless, colorless poison gas. 

Breathing in carbon monoxide can cause 

headaches, fatigue, diziness, nausea, vomit-

ting, confusion, fainting, siezures or death.

GENERAL HAZARDS

• 

For safety reasons, the manufacturer recommends that this 
equipment be installed, serviced and repaired by a Service 
Dealer or other competent, qualified electrician or installation 
technician who is familiar with applicable codes, standards 
and regulations. The operator also must comply with all such 
codes, standards and regulations.

• Adequate, unobstructed flow of cooling and ventilating air 

is critical to correct generator operation. Do not alter the 
installation or permit even partial blockage of ventilation 
provisions, as this can seriously affect safe operation of the 
generator. 

The generator MUST be installed and operated 

outdoors only.

• Keep hands, feet, clothing, etc., away from drive belts, fans, 

and other moving or hot parts. Never remove any drive belt or 
fan guard while the unit is operating.

CALIFORNIA PROPOSITION 65 WARNING

Engine exhaust and some of its constituents are known 

to the State of California to cause cancer, birth defects 

and other reproductive harm.

CALIFORNIA PROPOSITION 65 WARNING

This product contains or emits chemicals known to the 

State of California to cause cancer, birth defects and 

other reproductive harm.

Summary of Contents for CorePower/ES Generator

Page 1: ...com or 1 888 GENERAC NOT INTENDED FOR USE IN CRITICAL LIFE SUPPORT APPLICATIONS ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS SHOULD ATTEMPT INSTALLATION DEADLY EXHAUST FUMES OUTDOOR INSTALLATION ONLY TH...

Page 2: ...MANUAL THOROUGHLY If any portion of this manual is not understood contact the nearest Dealer for starting operating and servicing procedures Throughout this publication and on tags and decals affixed...

Page 3: ...by failing to follow simple and fundamental rules or precautions The manufacturer cannot anticipate every possible circumstance that might involve a hazard The warnings in this manual and on tags and...

Page 4: ...ive conductor AVOID DIRECT CONTACT WITH THE VICTIM Use a nonconducting implement such as a dry rope or board to free the victim from the live conductor If the victim is unconscious apply first aid and...

Page 5: ...d contact the carrier for claim procedures Concealed damage is understood to mean damage to the contents of a package that is not in evidence at the time of delivery but is discovered later To properl...

Page 6: ...s from any structure overhang or projections from the wall The generator should not be placed under a deck or other structure that is closed in and would limit or contain air flow These guidelines are...

Page 7: ...s windows ventilation fans or other air intakes Dig a rectangular area approximately five inches deep and about six inches longer and wider than the footprint of the generator Cover with polyurethane...

Page 8: ...upplied loose with the owners manual is installed into the groove of the fuel jet 9 Insert the Propane fuel jet into the end of the fuel inlet 10 Reinstall the hose and clamp onto the fuel inlet and s...

Page 9: ...the generator use the provided section of UL Listed or AGA approved flexible fuel line in accordance with local regulations The purpose of the flexible fuel line is to ensure that vibration from the...

Page 10: ...ain fastener and external tooth washer for reassembly 3 Remove the conduit connector plate from the output circuit breaker panel Remove the plastic hole plug from the conduit connector plate 4 Pass al...

Page 11: ...ock hasp will now protrude through the circuit breaker cover and it is recommended that once installation of the generator is completed a padlock be used to provide suitable security to the generator...

Page 12: ...simply replace any of the single pole circuit breakers supplied in the Transfer Switch distribution panel UTILITY CONNECTIONS 1 Install the Automatic Transfer Switch as close to the home main distribu...

Page 13: ...urce connections in the Transfer Switch 4 Cut to length strip identify and attach generator sensing wires marked N1 N2 T1 to correspondingly marked Fuses in the Transfer Switch 5 Cut to length strip i...

Page 14: ...the main distribution panel to the ON or CLOSED position Move the generator control panel switch to the Auto position To indicate that the generator control panel is able to identify the presence of...

Page 15: ...13 Notes...

Page 16: ...14 Installation Diagrams Drawing No 0H9267 B...

Page 17: ...15 Drawing No 0H9267 B Installation Diagrams...

Page 18: ...16 Installation Diagrams Drawing No 0J1064 C...

Page 19: ...17 Drawing No 0J1064 C Installation Diagrams...

Page 20: ...Part No 0J0193 Revision G 01 30 13 Printed in U S A...

Page 21: ...ERAC PELIGRO NO DISE ADO PARA USO EN APLICACIONES DE SOPORTE DE VIDA CR TICA SOLO ELECTRICISTAS O CONTRATISTAS CALIFICADOS DEBER N INTENTAR ESTAS INSTALACIONES GASES DE ESCAPE MORTALES INSTALACI N EN...

Page 22: ...on el concesionario m s cercano para conocer los procedimientos de arranque operaci n y servicio A lo largo de esta publicaci n y en lo que respecta a las etiquetas y calcoman as fijadas en el generad...

Page 23: ...ecauciones simples y fundamentales El fabricante no puede anticipar todas las posibles circunstancias que puedan involucrar peligros Las advertencias en este manual y en las etiquetas y calcoman as fi...

Page 24: ...abla para liberar a la v ctima del conductor vivo Si la v ctima est inconsciente aplique los primeros auxilios y consiga ayuda m dica inmediatamente Nunca use joyas al trabajar con este equipo Las joy...

Page 25: ...Da o oculto se entiende como el da o al contenido de un paquete que no se evidencia al momento de la entrega pero se descubre luego Para abrir apropiadamente el techo presione sobre el labio superior...

Page 26: ...0 pulgadas desde cualquier estructura colgante o proyecciones de la pared El generador no deber colocarse bajo una plataforma u otra estructura que este cerrada y limite o contenga el flujo de aire Es...

Page 27: ...tros ingresos de aire Cave un rea rectangular de aproximadamente cinco pulgadas de profundidad y seis pulgadas m s largo y ancho que la huella del generador Cubra con una pel cula de poliuretano y lle...

Page 28: ...le en la ranura de la boquilla de combustible 9 Inserte la boquilla de combustible propano en el extremo de la admisi n de combustible 10 Vuelva a instalar la manguera y la abrazadera en la admisi n d...

Page 29: ...la secci n proporcionada de l nea de combustible flexible aprobada por la AGA y listada en la UL de acuerdo con los reglamentos locales El prop sito de la l nea flexible de combustible es asegurar qu...

Page 30: ...a ensamblar 3 Desmonte la placa del conector de conducto del panel de salida de cortocircuitos Desmonte el tap n de pl stico del agujero de la placa del conector del conducto 4 Pase todos los cables...

Page 31: ...s de la cubierta del cortacircuitos y se recomienda que cuando se termine la instalaci n del generador se use un candado para proporcionar una seguridad adecuada al generador INSTALACI N DE LA BATER A...

Page 32: ...l panel de distribuci n del interruptor de transferencia CONEXIONES DE USO GENERAL 1 Instale el Interruptor Autom tico de Transferencia tan cerca como sea posible del lugar del panel principal de dist...

Page 33: ...en el interruptor de transferencia 4 Corte a la longitud pele identifique y sujete los cables de sensado del generador marcados N1 N2 y T1 a los correspondientes fusibles marcados en el interruptor de...

Page 34: ...cipal de distribuci n a la posici n de ENCENDIDO o CERRADO Mueva el interruptor del panel de control del generador a la posici n Auto Para indicar que el panel de control del generador es capaz de ide...

Page 35: ...33 Notas...

Page 36: ...No de parte 0J0193 Revisi n G 30 01 13 Impreso en los EE UU...

Page 37: ...R L UTILISATION N EST PAS PR VUE POUR LES MOYENS D ENTRETIEN ARTIFICIEL DE LA VIE SEULS DES LECTRICIENS OU DES PRESTATAIRES QUALIFI S DOIVENT TRAVAILLER SUR CES INSTALLATIONS GAZ D CHAPPEMENT MORTEL I...

Page 38: ...es proc dures de d marrage de fonctionnement et d entretien Dans tout ce manuel et sur les tiquettes et sur les autocollants appos s sur le g n rateur les blocs DANGER AVERTISSEMENT ATTENTION et REMAR...

Page 39: ...ations possibles qui peuvent impliquer un danger Les avertissements de ce manuel et figurant sur les tiquettes et les autocollants appos s sur l unit ne sont toutefois pas exhaustifs Si vous suivez un...

Page 40: ...is porter de bijoux lors du travail sur cet quipement Les bijoux peuvent tre conducteurs et entra ner une lectrocution ou peuvent s accrocher sur les composants mobiles entra nant des blessures RISQUE...

Page 41: ...visible lors de la livraison mais est d couvert plus tard Afin d ouvrir correctement le toit appuyer sur la l vre sup rieure centrale et rel cher le loquet Si la pression n est pas appliqu e du dessus...

Page 42: ...e 60 pouces minimum partir de toute structure d bord ou projection du mur Le g n rateur doit tre plac sous une plateforme ou autre structure qui est ferm e et limiterait ou contiendrait le d bit d air...

Page 43: ...s fen tres les ventilateurs soufflants ou autres admissions d air Creuser un trou rectangulaire d environ cinq pouces de profondeur et d environ six pouces plus longs et plus larges que l empreinte du...

Page 44: ...ure du gicleur de carburant 9 Ins rer le gicleur de carburant pour le propane dans l extr mit de l admission de carburant 10 R installer le tuyau et le collier sur le gicleur de carburant et serrer 11...

Page 45: ...6 Lors du raccordement de la canalisation de gaz au g n rateur utiliser la partie fournie du tuyau flexible de carburant certifi UL ou approuv AGA conform ment aux r glementations locales Le tuyau fle...

Page 46: ...cteur de sortie Garder la fixation et la rondelle ventail externe pour le remontage 3 Retirer la plaque du connecteur du conduit du panneau du disjoncteur de sortie Retirer le bouchon en plastique de...

Page 47: ...ra maintenant du couvercle du disjoncteur et apr s avoir effectu l installation du g n rateur il est recommand d utiliser un cadenas pour assurer la s curit ad quate du g n rateur INSTALLATION DE LA B...

Page 48: ...t l un des disjoncteurs unipolaires se trouvant dans le panneau de distribution du commutateur de transfert BRANCHEMENTS AU R SEAU PUBLIC 1 Installer le commutateur de transfert automatique aussi pr s...

Page 49: ...transfert 4 Couper dans le sens de la longueur d nuder identifier et fixer les fils de d tection du g n rateur marqu s N1 N2 et T1 aux fusibles marqu s correspondants dans le commutateur de transfert...

Page 50: ...ON Marche ou CLOSED Ferm e Mettre le commutateur du panneau de commande du g n rateur sur la position Auto Pour indiquer que le panneau de commande du g n rateur est capable d identifier la pr sence...

Page 51: ...49 Remarques...

Page 52: ...R f rence 0J0193 R vision G 30 01 13 Imprim aux tats Unis...

Page 53: ......

Page 54: ......

Reviews: