4
60 inches Minimum Distance All Around
36” if the surface has a fire resistant rating of at least one hour per NFPA 37
Existing Wall
No windows or openings in the wall permitted
within 5 feet from any point of the generator.
60” Minimum
60” Recommended
Minimum From Ends
Clearance from the ends and front of the generator
should be 36” minimum per NFPA 37. This would
include shrubs, trees and any kind of vegetation.
Clearance at the top should be a minimum of 60
inches from any structure, overhang or projections
from the wall. The generator should not be placed
under a deck or other structure that is closed in and
would limit or contain air flow.
These guidelines are based upon the
requirements of NFPA 37 and the
manufacturer’s requirement for air flow
for proper operation. Local codes may
be different and more restrictive than
what is described here.
Top of Generator
Generator
NOTE:
Failure to follow these minimum clearance guidelines may result in the generator failing inspection by the local
building, electrical or fire inspector requiring the generator be reinstalled in the correct location.
MINIMUM CLEARANCE REQUIREMENTS
Summary of Contents for CorePower/ES Generator
Page 15: ...13 Notes...
Page 16: ...14 Installation Diagrams Drawing No 0H9267 B...
Page 17: ...15 Drawing No 0H9267 B Installation Diagrams...
Page 18: ...16 Installation Diagrams Drawing No 0J1064 C...
Page 19: ...17 Drawing No 0J1064 C Installation Diagrams...
Page 20: ...Part No 0J0193 Revision G 01 30 13 Printed in U S A...
Page 35: ...33 Notas...
Page 36: ...No de parte 0J0193 Revisi n G 30 01 13 Impreso en los EE UU...
Page 51: ...49 Remarques...
Page 52: ...R f rence 0J0193 R vision G 30 01 13 Imprim aux tats Unis...
Page 53: ......
Page 54: ......