45 / 48
1283
12 Technical
data
Materials
Housing
PPO 30 % glass reinforced
Operating conditions
Ambient temperature
0 to + 60 °C
Storage temperature
0 to + 60 °C
Electrical data
Power supply
24 V DC ±15 %
24 V 50/60 Hz ±15 %
100-250 V 50/60 Hz ±15 %
Power consumption
4 VA / 4 W
(without motor load and without options)
Analogue inputs
Set value input
0/4-20 mA
Ri = 50
Ω
Actual value input In1
for connection of a
potentiometer R > 500
Ω
Actual value input In2
0/4-20 mA (2/3-wire)
(optional)
Analogue output
(
optional
)
Actual value output
4-20 mA
Load resistor
< 600
Ω
Relay outputs
Switching voltage
U
N
250 V AC,
U
N
24 V DC
Switching current
I
N
5A AC @ 250V AC
I
N
5A DC @ 24V DC
Switch rating max.
1250 VA, 150 W
Operating and display elements
Display 3-digit
7-segment
display
Keys
4 membrane protected
fascia
keys
LED
4 status LEDs
General information
Protection class to EN 60529
IP 40
EMC directive
Interference resistance
EN 61000-6-2
Interference emission
EN 61000-6-4 (class B)
Weight
510 g
Dimensions L x W x H
See dimensional drawing
Mounting position
Optional
13 Order
data
Accessory Code
Accessory Z
Options Code
Without 00
Current output 4-20 mA and
actual value input for process control
01
Field bus
Code
Without 000
Mounting version
Code
Direct mounting
00
Panel mounting
10
Device version
Code
3-point controller
01
Order example
1283
000
Z
00
01
00
C4
Type
1283
Field bus (code)
000
Accessory (code)
Z
Mounting version (code)
00
Device version (code)
01
Options (code)
00
Voltage / Frequency (code)
C4
Voltage / Frequency
Code
24 V DC
C1
24 V 50/60 Hz
C4
100-250 V 50/60 Hz
O4
Controller data
Dead zone (Switching voltage) 1 % (default settings)
≥
0.5 % (adjustable)
Controller version
3-point controller
Summary of Contents for 1283
Page 9: ...9 48 1283 bl blau or orange gr grau ...
Page 31: ...31 48 1283 bl blue or orange gr grey ...
Page 46: ...46 48 1283 ...
Page 47: ...47 48 1283 ...