10.1 Parameter
table
Display
Function
Value range
Factory setting
OFF
Controller does not react to set value changes
AUTO
Controller reacts to external set value signal
MANUAL
Controller reacts to manual set value specification
Error
Error messages
P:01
Permissible system deviation (dead zone)
0.5...25.0
1.0
P:02**
Type of set value signal
0...20 mA
4...20 mA
4...20 mA
P:03*
Selection of used actual value input
In 1
In 2
In 2
P:04*
Type of actual value signal
0...20 mA
4...20 mA
4...20 mA
P:05*
Function of analogue signal output
Set
Act
Pos
Set
P:06
Function of display indication
Set
Act
Pos
Set
P:07
Lower position of control range - closing limit
0.0...100
0.0
P:08
Upper position of control range - stroke limitation
0.0...100
100
P:09
Scaling of the set value input
OFF
ON
S:Lo
S:Hi
OFF
I:no / I:cP
Starting automatic initialisation
run
rus
* Parameter only available with optional additional external actual value signal
** Parameter unavailable when scaling of the set value signal is active (P:09 “ON”)
10.2 Explanation of parameters
10.2.1 System deviation – P:01
Defines the maximum permissible deviation (dead zone) between set value and actual
value.
10.2.2 External set value signal – P:02
Defines the type of external set value signal 0...20 mA / 4...20 mA.
⇒
Only available when P:09 “OFF”