10.4.5 Fitting the Logic Element NOT (Sealing Package)
Requirement:
•
Logic element NOT is only provided in connection with the pneumatic block
T.VIS/NOT!
Carry out the following steps:
1.
Fit the logic element NOT (64) in reverse order.
!
Place the logic element NOT, with adapter plate and seal, on the pneumatic
block (8) as shown in the illustration.
!
When inserting and tightening the screws, be careful to use existing threads.
Tightening torque 1.5 Nm (1.0 lbft).
Fig.71
®
Done
Hint!
Faulty assembly may cause malfunctions, as the spring force backup
is then not given.
Maintenance
Dismantling the Control Top into its Components
430BAL010697EN_2
98
15.04.2020