VLT
®
5000 Series
If low-frequency resonance problems are encoun-
tered, the time set must be longer.
117
117 Resonance dampening
(RESONANCE DAMP.)
Value:
0 - 500 %
✭
100 %
Function:
High-frequency resonance problems can be elimi-
nated by setting parameters 117 and 118.
Description of choice:
For less resonance oscillation, the value of parame-
ter 118 must be increased.
118
118 Resonance dampening time constant
(DAMP.TIME CONST.)
Value:
5 - 50 ms
✭
5 ms
Function:
High-frequency resonance problems can be elimi-
nated by setting parameters 117 and 118.
Description of choice:
Choose the time constant that provides the best
dampening.
119
119 High starting torque
(HIGH START TORQ.)
Value:
0.0 - 0.5 sec.
✭
0.0 sec.
Function:
In order to secure a high starting torque, approx. 2 x
I
VLT,N
for max. 0.5 sec. is allowed. However, the cur-
rent is limited by the protection limit of the VLT
frequency converter (inverter).
Description of choice:
Set the necessary time in which a high starting
torque is desired.
120
120 Start delay (START DELAY)
Value:
0.0 - 10.0 sec.
✭
0.0 sec.
Function:
This parameter enables a delay of the starting time.
The VLT frequency converter begins with the start
function selected in parameter 121.
Description of choice:
Set the desired time until acceleration is to begin.
121
121 Start function (START FUNCTION)
Value:
DC hold in start delay time
(DC HOLD/DELA Y TIME)
[0]
DC brake in start delay time
(DC BRAKE/DELA Y TIME)
[1]
✭
Coasting in start delay time
(COAST/DELA Y TIME)
[2]
Start frequency/voltage clockwise.
(CLOCKWISE OPERA TION)
[3]
Start frequency/voltage in reference direction
(HORIZONT AL OPERA TION)
[4]
VVC
p l u s
clockwise
(VVC+ CLOCKWISE)
[5]
Function:
This is where the desired state during start delay
(parameter 120) is selected.
Description of choice:
Select
DC hold in the start delay time
[0] so as to
energize the motor with a DC holding current (pa-
rameter 124) in the start delay time.
Select
DC brake in the start delay time
[1] so as to
energize the motor with a DC braking current (pa-
rameter 125) in the start delay time.
Select
Coasting in the start delay time
[2] and the
motor will not be controlled by the VLT frequency
converter during the start delay time (inverter off).
Start frequency/voltage clockwise
[3] and
VVC
plus
clockwise
[5] is typically used in hoisting applications.
Start frequency/voltage in reference direction
[4] is
used especially in applications with counterweight.
Select
Start frequency/voltage clockwise
[3] so as to
have the function described in parameter 130 and
131 in the start delay time.
The output frequency will equal the setting of the
start frequency in parameter 130, and the output
voltage will equal the setting of the start voltage in
parameter 131. Regardless of the value assumed by
the reference signal, the output frequency will equal
the setting of the start frequency in parameter 130
and the output voltage will correspond to the setting
of the start voltage in parameter 131.
This functionality is used typically in hoisting applica-
tions.
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.51.A1.02 - VLT is a registered Danfoss trade mark
116
Summary of Contents for ARIETE
Page 7: ......
Page 10: ......
Page 18: ...Niro Soavi S p A FIGURE 2 2 2 2C001E0C DOC 2 2 2 ...
Page 52: ...Niro Soavi S p A FIGURE 3 2 1 2 1 D A B C FIGURE 3 2 2 3C001E0C DOC 3 2 3 ...
Page 76: ...Niro Soavi S p A 3 9 SPECIAL FEATURES OF NON STANDARD MACHINES BLANK PAGE Ricerca Guasti 21 2 ...
Page 93: ...Niro Soavi S p A 4C042E0C DOC 4 4 8 FIGURE 4 4 3 FIGURE 4 4 3 ...
Page 109: ...Niro Soavi S p A FIGURE 4 6 1 4c063e0c doc 4 6 3 ...
Page 134: ...Niro Soavi S p A FIGURE 4 9 1 4c091e0c doc 4 9 4 ...
Page 155: ...Niro Soavi S p A 5C001E0C DOC 5 3 3 ...
Page 160: ......
Page 162: ......
Page 164: ......
Page 166: ......
Page 168: ......
Page 170: ......
Page 172: ......
Page 174: ......
Page 176: ......
Page 178: ......
Page 180: ......
Page 182: ......
Page 184: ......
Page 186: ......
Page 188: ......
Page 190: ......
Page 192: ......
Page 195: ......
Page 201: ......
Page 202: ......
Page 203: ......
Page 211: ......
Page 212: ......
Page 213: ......
Page 214: ......
Page 215: ......
Page 216: ......
Page 217: ......
Page 218: ......
Page 219: ......
Page 220: ......
Page 221: ......
Page 222: ......
Page 223: ......
Page 224: ......
Page 225: ......
Page 226: ......
Page 227: ......
Page 228: ......
Page 229: ......
Page 230: ......
Page 231: ......
Page 232: ......
Page 233: ......
Page 234: ......
Page 235: ......
Page 236: ......
Page 237: ......
Page 238: ......
Page 239: ......
Page 240: ......
Page 241: ......
Page 242: ......
Page 243: ......
Page 244: ......
Page 245: ......
Page 246: ......
Page 247: ......
Page 248: ......
Page 249: ......
Page 250: ......
Page 254: ......
Page 255: ......
Page 264: ......
Page 265: ......
Page 266: ......
Page 270: ......
Page 272: ......
Page 330: ......
Page 331: ......
Page 332: ......
Page 390: ...VLT 5000 Series MG 51 A1 02 VLT is a registered Danfoss trade mark 56 ...
Page 429: ...VLT 5000 Series MG 51 A1 02 VLT is a registered Danfoss trade mark 95 Special functions ...
Page 542: ......
Page 543: ......
Page 544: ......
Page 546: ......
Page 547: ......
Page 548: ......
Page 549: ......
Page 550: ......
Page 551: ......
Page 554: ......
Page 555: ......
Page 556: ......