VLT
®
5000 Series
Description of choice:
If
Local not active
[0] is selected, a possible setting
of
Local reference via parameter 003
is blocked.
It is only possible to change to
Local not active
[0]
from one of the other setting options in parameter
013, when the VLT frequency converter has been
set to
Remote control
[0] in parameter 002.
LCP control and open loop
[1] is used when the
speed is to be adjustable (in Hz) via parameter 003,
when the VLT frequency converter has been set to
Local control
[1] in parameter 002.
If parameter 100 has not been set to
Speed control
open loop
[0], switch to
Speed control open loop
[0]
LCP digital control and open loop
[2] functions as
LCP control and open loop
[1] , the only difference
being that when parameter 002 has been set to
Lo-
cal operation
[1], the motor is controlled via the
digital inputs, according to the list in section
Shift be-
tween local and remote control
.
LCP control/as parameter 100
[3] is selected if the
reference is to be set via parameter 003.
LCP digital control/as parameter 100
[4] functions as
LCP control/as parameter 100 [3], although, when
parameter 002 has been set to
Local operation
[1],
the motor may be controlled via the digital inputs in
accordance with the list in section
Shift between lo-
cal and remote control
.
NB!:
Shift from Remote control to LCP digital control and
open loop:
The present motor frequency and direction of rota-
tion must be maintained. If the present direction of
rotation does not correspond to the reversing signal
(negative reference), the motor frequency f
M
will be
set at 0 Hz.
Shift from LCP digital control and open loop to Re-
mote control:
The selected configuration (parameter 100) will be
active. Shifts are effected without any abrupt move-
ment.
Shift from Remote control to LCP control/as parame-
ter 100 or LCP digital control/as parameter 100.
The present reference will be maintained. If the ref-
erence signal is negative, the local reference will be
set at 0.
Shift from LCP control/as parameter 100 or LCP re-
mote control as parameter 100 to Remote control.
The reference will be replaced by the active refer-
ence signal from the remote control.
014
014 Local stop (LOCAL STOP)
Value:
Not possible (DISABLE)
[0]
✭
Possible (ENABLE)
[1]
Function:
This parameter disables/enables the local stop func-
tion in question from the control panel.
This key is used when parameter 002 has been set
for
Remote control
[0] or
Local
[1].
Description of choice:
If
Disable
[0] is selected in this parameter, the
[STOP] key will be inactive.
NB!:
If
Enable
is selected,
the [STOP] key overrules all Start commands.
015
015 Local jog (LOCAL JOGGING)
Value:
✭
Not possible (DISABLE)
[0]
Possible (ENABLE)
[1]
Function:
In this parameter, the jog function can be enabled/
disabled on the control panel.
The key can be used when parameter 002 has been
set for
Remote control [0]
or
Local
[1].
Description of choice:
If
Disable
[0] is selected in this parameter, the [JOG]
key will be inactive.
016
016 Local reversing
(LOCAL REVERSING)
Value:
✭
Not possible (DISABLE)
[0]
Possible (ENABLE)
[1]
Function:
In this parameter, the reversing function can be en-
abled/disabled on the control panel.
This key can only be used if parameter 002 has
been set to
Local operation
[1] and parameter 013 to
LCP control with open loop
[1] or
LCP control as pa-
rameter 100
[3].
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.51.A1.02 - VLT is a registered Danfoss trade mark
108
Summary of Contents for ARIETE
Page 7: ......
Page 10: ......
Page 18: ...Niro Soavi S p A FIGURE 2 2 2 2C001E0C DOC 2 2 2 ...
Page 52: ...Niro Soavi S p A FIGURE 3 2 1 2 1 D A B C FIGURE 3 2 2 3C001E0C DOC 3 2 3 ...
Page 76: ...Niro Soavi S p A 3 9 SPECIAL FEATURES OF NON STANDARD MACHINES BLANK PAGE Ricerca Guasti 21 2 ...
Page 93: ...Niro Soavi S p A 4C042E0C DOC 4 4 8 FIGURE 4 4 3 FIGURE 4 4 3 ...
Page 109: ...Niro Soavi S p A FIGURE 4 6 1 4c063e0c doc 4 6 3 ...
Page 134: ...Niro Soavi S p A FIGURE 4 9 1 4c091e0c doc 4 9 4 ...
Page 155: ...Niro Soavi S p A 5C001E0C DOC 5 3 3 ...
Page 160: ......
Page 162: ......
Page 164: ......
Page 166: ......
Page 168: ......
Page 170: ......
Page 172: ......
Page 174: ......
Page 176: ......
Page 178: ......
Page 180: ......
Page 182: ......
Page 184: ......
Page 186: ......
Page 188: ......
Page 190: ......
Page 192: ......
Page 195: ......
Page 201: ......
Page 202: ......
Page 203: ......
Page 211: ......
Page 212: ......
Page 213: ......
Page 214: ......
Page 215: ......
Page 216: ......
Page 217: ......
Page 218: ......
Page 219: ......
Page 220: ......
Page 221: ......
Page 222: ......
Page 223: ......
Page 224: ......
Page 225: ......
Page 226: ......
Page 227: ......
Page 228: ......
Page 229: ......
Page 230: ......
Page 231: ......
Page 232: ......
Page 233: ......
Page 234: ......
Page 235: ......
Page 236: ......
Page 237: ......
Page 238: ......
Page 239: ......
Page 240: ......
Page 241: ......
Page 242: ......
Page 243: ......
Page 244: ......
Page 245: ......
Page 246: ......
Page 247: ......
Page 248: ......
Page 249: ......
Page 250: ......
Page 254: ......
Page 255: ......
Page 264: ......
Page 265: ......
Page 266: ......
Page 270: ......
Page 272: ......
Page 330: ......
Page 331: ......
Page 332: ......
Page 390: ...VLT 5000 Series MG 51 A1 02 VLT is a registered Danfoss trade mark 56 ...
Page 429: ...VLT 5000 Series MG 51 A1 02 VLT is a registered Danfoss trade mark 95 Special functions ...
Page 542: ......
Page 543: ......
Page 544: ......
Page 546: ......
Page 547: ......
Page 548: ......
Page 549: ......
Page 550: ......
Page 551: ......
Page 554: ......
Page 555: ......
Page 556: ......