VLT
®
5000 Series
3. The values are obtained by means of manual
measurements:
-
R
S
can be calculated by measuring the resis-
tance R
PHASE-to-PHASE
between two phase
terminals. If R
PHASE-to-PHASE
is lower than 1-2
ohm (typically motors >4-5.5 kW, 400 V), a spe-
cial ohm-meter should be used (Thomson bridge
or similar). R
S
= 0.5 x R
PHASE-to-PHASE
4. The factory settings of R
S
, selected by the VLT
frequency converter itself on the basis of the mo-
tor nameplate data, are used.
NB!:
If the setting in parameter 102-109 is
changed, the parameters 110-118 will return
to factory setting.
109
109 Stator reactance
(STATOR REACT.)
Value:
✭
depends on the choice of motor
Function:
After setting motor data in parameters 102-106, a
number of adjustments of various parameters are
made automatically , including the stator resistance
X
S
. The shaft performance can be improved by fine-
tuning R
S
and X
S
, see procedure below.
Description of choice:
X
S
can be set as follows:
1. Automatic motor adaptation, where the VLT fre-
quency converter measures on the motor to
determine the value. All compensations are reset
to 100%.
2. The values are stated by the motor supplier.
3. These values are obtained by means of manual
measurements:
- X
S
can be calculated by connecting a motor to
mains and measuring the phase-to-phase voltage
U
L
as well as the idling current I .
Alternatively , these values can be recorded dur-
ing operation in idle running state at the rated
motor frequency f
M,N
, slip compensation (par.
115) = 0% and load compensation at high speed
(par. 114) = 100%.
X
S
=
U
L
p
3 x l8
4. The factory settings of X
S
, selected by the VLT
frequency converter itself on the basis of the mo-
tor nameplate data, are used.
NB!:
If the setting in parameter 102-109 is
changed, the parameters 110-118 will return
to factory setting.
110
110 Motor magnetizing, 0 rpm
(MOT. MAGNETIZING)
Value:
0 - 300 %
✭
100 %
Function:
This parameter can be used if a different thermal
load on the motor is desired when running at low
speed.
This parameter is used in connection with parameter
111.
Description of choice:
Enter a value stated as a percentage of the rated
magnetizing current.
Too low setting may lead to a reduced torque on the
motor shaft.
111
111 Min. frequency normal magnetizing
(MIN FR NORM MAGN)
Value:
0.1 - 10.0 Hz
✭
1.0 Hz
Function:
This parameter is used in connection with parameter
110. See drawing in parameter 110.
Description of choice:
Set the required frequency (for normal magnetizing
current). If the frequency is set lower than the motor
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.51.A1.02 - VLT is a registered Danfoss trade mark
114
Summary of Contents for ARIETE
Page 7: ......
Page 10: ......
Page 18: ...Niro Soavi S p A FIGURE 2 2 2 2C001E0C DOC 2 2 2 ...
Page 52: ...Niro Soavi S p A FIGURE 3 2 1 2 1 D A B C FIGURE 3 2 2 3C001E0C DOC 3 2 3 ...
Page 76: ...Niro Soavi S p A 3 9 SPECIAL FEATURES OF NON STANDARD MACHINES BLANK PAGE Ricerca Guasti 21 2 ...
Page 93: ...Niro Soavi S p A 4C042E0C DOC 4 4 8 FIGURE 4 4 3 FIGURE 4 4 3 ...
Page 109: ...Niro Soavi S p A FIGURE 4 6 1 4c063e0c doc 4 6 3 ...
Page 134: ...Niro Soavi S p A FIGURE 4 9 1 4c091e0c doc 4 9 4 ...
Page 155: ...Niro Soavi S p A 5C001E0C DOC 5 3 3 ...
Page 160: ......
Page 162: ......
Page 164: ......
Page 166: ......
Page 168: ......
Page 170: ......
Page 172: ......
Page 174: ......
Page 176: ......
Page 178: ......
Page 180: ......
Page 182: ......
Page 184: ......
Page 186: ......
Page 188: ......
Page 190: ......
Page 192: ......
Page 195: ......
Page 201: ......
Page 202: ......
Page 203: ......
Page 211: ......
Page 212: ......
Page 213: ......
Page 214: ......
Page 215: ......
Page 216: ......
Page 217: ......
Page 218: ......
Page 219: ......
Page 220: ......
Page 221: ......
Page 222: ......
Page 223: ......
Page 224: ......
Page 225: ......
Page 226: ......
Page 227: ......
Page 228: ......
Page 229: ......
Page 230: ......
Page 231: ......
Page 232: ......
Page 233: ......
Page 234: ......
Page 235: ......
Page 236: ......
Page 237: ......
Page 238: ......
Page 239: ......
Page 240: ......
Page 241: ......
Page 242: ......
Page 243: ......
Page 244: ......
Page 245: ......
Page 246: ......
Page 247: ......
Page 248: ......
Page 249: ......
Page 250: ......
Page 254: ......
Page 255: ......
Page 264: ......
Page 265: ......
Page 266: ......
Page 270: ......
Page 272: ......
Page 330: ......
Page 331: ......
Page 332: ......
Page 390: ...VLT 5000 Series MG 51 A1 02 VLT is a registered Danfoss trade mark 56 ...
Page 429: ...VLT 5000 Series MG 51 A1 02 VLT is a registered Danfoss trade mark 95 Special functions ...
Page 542: ......
Page 543: ......
Page 544: ......
Page 546: ......
Page 547: ......
Page 548: ......
Page 549: ......
Page 550: ......
Page 551: ......
Page 554: ......
Page 555: ......
Page 556: ......