9
Notes on the tables below
Diagnostic code
The diagnostic register of the module includes both the diagnostic selector and the
diagnostic code. This diagnostic code, which is represented in bits 11 to 0 of the register,
is specified in Table 9-3 and onwards. However, it is the code of the entire diagnostic
register that is indicated. To obtain the diagnostic code specified in the documentation,
logically AND the code of the diagnostic register indicated with the code 07FF
hex
.
Example: ANDing the
diagnostic code
Diagnostic code indicated: E281
hex
(Example for an error in VersaSafe mode)
Diagnostic code specified in the documentation: X281
hex
As the first digit is never relevant, the code always starts with an X.
If the same error can occur at different outputs/channels, a generalizing diagnostic code is
indicated with an n where the error location is specified.
Generalizing diagnostic code specified in the documentation: X03n
hex
For some errors a single channel is specified as the error location (e.g., OUT0_Ch1).
Some errors only occur for outputs parameterized for two-channel operation. Here, the
channel pair is specified as the error location (e.g., OUT0_Ch1&2).
Example: Channels in the
diagnostic code
Safe output errors (Table 9-3)
Table 9-2
Relationship between the diagnostic code indicated and the diagnostic code specified in the documentation
15
14
13
12
11
10
...
0
Diagnostic register in the
event of an error
Diagnostic selector
Not
relevant
Diagnostic code
Assignment of the diagnostic
register in the event of an
error
1
1
1
0
Diagnostic code
Diagnostic code
indicated
hex
E
2
8
1
bin
1
1
1
0
0
0
1
0
1
0
0
0
0
0
0
1
Mask (0FFF
hex
)
bin
0
0
0
0
1
1
1
1
1
1
1
1
1
1
1
1
Diagnostic code in the
documentation
bin
0
0
0
0
0
0
1
0
1
0
0
0
0
0
0
1
hex
0 ->
X
(not relevant)
2
8
1
Error cause
Error code (hex)
Signal error at alarm input
X0Bn
X0B0: OUT0_Ch1; X0B1: OUT1_Ch1
X0B7: OUT0_Ch2; X0B8: OUT1_Ch2
X0B
n
Signal error at alarm input
X0B
n
Error location
This means, for example:
X0B0
Signal error at alarm input at OUT0_Ch1 (relay output 0 channel 1)
X0B8
Signal error at alarm input at OUT1_Ch2 (relay output 1 channel 2)
9-2
User manual IC220SDL840 -
May 2018
GFK-2734