8
When connecting the supply voltages, use the diagnostic and status indicators to check
whether the module has started up correctly or whether any errors are indicated. For
instructions on how to proceed in the event of an error, please refer to Section "Errors:
Messages and removal" on page 9-1.
8.2
Restart after replacing a safety module
8.2.1
Replacing a safety module
If replacing a module, proceed as described for assembly and removal (see Section
"Assembly, removal, and electrical installation" on page 4-1).
Ensure that the new safe safety module is mounted at the correct position in the local bus.
The new module must meet the following requirements:
–
Same device type
–
Same or later version
8.2.2
Restart
Once the safety module has been replaced, proceed as described for initial startup (see
Section "Initial startup" on page 8-1).
The parameterization of the previous module remains the same and is transmitted to the
new module when the system is started.
Program the safety function.
User manuals for the function blocks used
Documentation for the configurable logic module used
(VersaSafe)
Documentation for the controller used (PROFIsafe)
For PROFIsafe: When verifying the safety function, check
whether the F_iPar_CRC parameter is greater than 0 for all
devices. If not, modify the settings.
Checklist "Validation" on page C-6
Quick start guide for configuring VersaPoint modules with
safe inputs or outputs under PROFIsafe on your controller
Perform a function test and validation. Check whether the
safety function responds as planned during programming
and parameterization.
Checklist "Validation" on page C-6
Table 8-1
Steps for startup [...]
Step
Relevant section and literature
WARNING: Electric shock/unintentional machine startup
Do not assemble or remove the module while the power is connected.
Before assembling or removing the module, disconnect the power to the module and the
entire VersaPoint station and ensure that it cannot be switched on again.
Make sure the entire station is reassembled before switching the power back on.
Observe the diagnostic indicators and any diagnostic messages.
The system may only be started provided neither the station nor the system poses a
hazard.
8-2
User manual IC220SDL840 -
May 2018
GFK-2734