6
Typical parameterization
According to the "Value range of switch-off time" and "Switch-off time" parameters, in this
example, the shutdown time is 40 x 10 ms = 400 ms.
According to the "Value range of switch-off delay for stop category 1" and "Switch-off delay
for stop category 1" parameters, in this example, the switch-off delay is 30 x 1 s = 30 s.
Short circuit
Output to ground
or
output to FE
No
None
No
The error is not detected.
To protect the relay output against overload, observe the notes
on protecting the relay outputs in
Table 6-13
Safety-related segment circuit: Assignment with two-channel actuators
Error type
Detection Diagnostics Loss of
SF
Remark
Table 6-14
Safety-related segment circuit: Assignment with two-channel actuators; typical parameterization
Parameterization
Parameterized as
Remark
Channel 1
Channel 2
Assignment
Used
Used
Output
Two-channel
Two-channel
Alarm input IN1
Do not evaluate
Do not evaluate
Alarm input IN2
Do not evaluate
Do not evaluate
Switch-off delay for stop
category 1
Enabled
Enabled
Or disabled
Switch-off delay for stop
category 1
30
30
Application-specific
Value range of switch-off
delay for stop category 1
Value in s
Value in s
Application-specific
Enable
(VersaSafe only)
Enabled
Enabled
Or disabled
6-24
User manual IC220SDL840 -
May 2018
GFK-2734