4
4.1.3
Setting the DIP switches
The module has a 2-pos. and a 10-pos. DIP switch.
The DIP switches are located on the left-hand side of the safety module.
Figure 4-1
DIP switches
2-pos. DIP switch:
The transmission speed and the mode are set via the 2-pos. DIP switch.
Left switch:
Transmission speed
The transmission speed can be set to 500 kbaud or 2 Mbaud.
The transmission speed is set to 2 Mbaud by default.
Right switch: Mode
For PROFIsafe, set Mode 1.
For VersaSafe, set Mode 2.
10-pos. DIP switch:
Protocol/address
The protocol (VersaSafe or PROFIsafe) is set via the 10-pos. DIP switch. Use this DIP
switch to set the VersaSafe or PROFIsafe address (F-Address).
VersaSafe
: Set the VersaSafe address specified by the configurable logic module.
PROFIsafe
: Set the PROFIsafe address for the PROFIsafe device. PROFIsafe addresses
1 to 1022 are permitted. The terminal is detected as a PROFIsafe device by means of the
set PROFIsafe address.
The DIP switch is set to 3FF
hex
by default. This address is not valid for a VersaSafe or
PROFIsafe system, therefore a valid address must be set.
A
Switch for setting the transmission speed and the mode
B
Switch for setting the protocol or the address (for PROFIsafe, VersaSafe)
500KBD
2MBD Mode1
Mode2
9 8 7 6 5 4 3 2
1 0
F-Address
off
on
500KBD
2MBD Mode1
Mode2
A
A
B
B
9 8 7 6 5 4 3 2
1 0
77221009
F-Address
off
on
Only use devices with a uniform transmission speed within a VersaPoint station (a local
bus). It is not possible to operate a mixture of devices with different transmission speeds.
For more detailed information about the VersaSafe address, please refer to the
documentation for the configurable logic module used.
4-2
User manual IC220SDL840 -
May 2018
GFK-2734