Chapter B Diagnostic messages for parameter errors
B-3
B 3
Diagnostic messages for parameter errors
B 3.1
Diagnostic messages for F-Parameters and iParameters for
PROFIsafe
Table B-2
F-Parameter parameter errors
Error code
Error cause
Remedy
dec
hex
64
40
The parameterized F_Destination_Address does not
match the PROFIsafe address set on the safety module
(F-Module).
Make sure that the PROFIsafe address of the
safety module and the value in
F_Destination_Address are the same.
65
41
Invalid parameterization of F_Destination_Address.
Addresses 0000
hex
and FFFF
hex
are not permitted.
Correct value.
66
42
Invalid parameterization of F_Source_Address.
Addresses 0000
hex
and FFFF
hex
are not permitted.
Correct value.
67
43
Invalid parameterization of F_WD_Time.
A monitoring time of 0 ms is not permitted.
Correct value.
68
44
Invalid parameterization of F_SIL.
The safety module (F-Module) cannot support the
required SIL.
Use a device with the required SIL.
The safety module achieves SIL 3, maximum.
69
45
Invalid parameterization of F_CRC_Length.
The CRC length generated by the safety module
(F-Module) does not match the required length.
Check device description.
70
46
Invalid F-Parameter record version.
The safety module (F-Module) version does not match
the required version.
Check device description.
Only V2 mode permitted.
71
47
The checksum determined by the safety module
(F-Module) via the PROFIsafe parameters (CRC1)
does not match the CRC1 transmitted in the parameter
telegram.
Check F-Parameters, repeat calculation.
255
FF
During active process data communication, a new
F-Parameter block was received, which differs from the
F-Parameter block currently used.
Only send modified parameter data when
process data communication is not active.
Incorrect type ID for the F-Parameter block
(F_Block_ID).
Check device description.