B-40
F35 Multiple Feeder Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
5DA3
Ground Instantaneous Overcurrent 1 Delay
0 to 600
s
0.01
F001
0
5DA4
Ground Instantaneous Overcurrent 1 Reset Delay
0 to 600
s
0.01
F001
0
5DA5
Ground Instantaneous Overcurrent 1 Block
0 to 4294967295
---
1
F300
0
5DA7
Ground Instantaneous Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
5DA8
Ground Instantaneous Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
5DA9
Reserved (8 items)
0 to 1
---
1
F001
0
5DB1
...Repeated for Ground Instantaneous Overcurrent 2
5DC2
...Repeated for Ground Instantaneous Overcurrent 3
5DD3
...Repeated for Ground Instantaneous Overcurrent 4
5DE4
...Repeated for Ground Instantaneous Overcurrent 5
5DF5
...Repeated for Ground Instantaneous Overcurrent 6
5E06
...Repeated for Ground Instantaneous Overcurrent 7
5E17
...Repeated for Ground Instantaneous Overcurrent 8
5E28
...Repeated for Ground Instantaneous Overcurrent 9
5E39
...Repeated for Ground Instantaneous Overcurrent 10
5E4A
...Repeated for Ground Instantaneous Overcurrent 11
5E5B
...Repeated for Ground Instantaneous Overcurrent 12
Incipient Cable Fault Detector Actual Values (Read Only) (6 modules)
5EC0
Incipient Cable Fault Detector 1 Phase A Counter
0 to 65535
---
1
F001
0
5EC1
Incipient Cable Fault Detector 1 Phase B Counter
0 to 65535
---
1
F001
0
5EC2
Incipient Cable Fault Detector 1 Phase C Counter
0 to 65535
---
1
F001
0
5EC3
...Repeated for Incipient Cable Fault Detector 2
5EC6
...Repeated for Incipient Cable Fault Detector 3
5EC9
...Repeated for Incipient Cable Fault Detector 4
5ECC
...Repeated for Incipient Cable Fault Detector 5
5ECF
...Repeated for Incipient Cable Fault Detector 6
Incipient Cable Fault Detector Command (Read/Write Setting) (6 modules)
5ED8
Incipient Cable Fault Detector 1 Clear Counters
0 to 1
---
1
F126
0 (No)
5ED9
...Repeated for Incipient Cable Fault Detector 2
5EDA
...Repeated for Incipient Cable Fault Detector 3
5EDB
...Repeated for Incipient Cable Fault Detector 4
5EDC
...Repeated for Incipient Cable Fault Detector 5
5EDD
...Repeated for Incipient Cable Fault Detector 6
Setting Groups (Read/Write Setting)
5F70
Setting Group for Modbus Comms (0 means group 1)
0 to 5
---
1
F001
0
5F71
Setting Groups Block
0 to 4294967295
---
1
F300
0
5F73
FlexLogic Operands to Activate Groups 2 through 6 (5
items)
0 to 4294967295
---
1
F300
0
5F7D
Setting Group Function
0 to 1
---
1
F102
0 (Disabled)
5F7E
Setting Group Events
0 to 1
---
1
F102
0 (Disabled)
Setting Groups (Read Only)
5F7F
Current Setting Group
0 to 5
---
1
F001
0
Setting Group Names (Read/Write Setting)
5F8C
Setting Group 1 Name
---
---
---
F203
(none)
5F94
Setting Group 2 Name
---
---
---
F203
(none)
5F9C
Setting Group 3 Name
---
---
---
F203
(none)
5FA4
Setting Group 4 Name
---
---
---
F203
(none)
5FAC
Setting Group 5 Name
---
---
---
F203
(none)
5FB4
Setting Group 6 Name
---
---
---
F203
(none)
Autoreclose (Read/Write Setting) (6 modules)
6200
Autoreclose 1 Function
0 to 1
---
1
F102
0 (Disabled)
6201
Autoreclose 1 Initiate
0 to 4294967295
---
1
F300
0
6203
Autoreclose 1 Block
0 to 4294967295
---
1
F300
0
6205
Autoreclose 1 Max Number of Shots
1 to 4
---
1
F001
1
Table B–10: MODBUS MEMORY MAP (Sheet 32 of 64)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for UR F35 Series
Page 10: ...x F35 Multiple Feeder Protection System GE Multilin TABLE OF CONTENTS ...
Page 366: ...5 238 F35 Multiple Feeder Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 426: ...10 12 F35 Multiple Feeder Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 454: ...A 28 F35 Multiple Feeder Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 620: ...F 12 F35 Multiple Feeder Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 630: ...H 8 F35 Multiple Feeder Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 640: ...x F35 Multiple Feeder Protection System GE Multilin INDEX ...