GE Multilin
F35 Multiple Feeder Protection System
5-209
5 SETTINGS
5.7 CONTROL ELEMENTS
5
A general form of a PID regulator in the
s
domain is shown below.
Figure 5–94: PID BLOCK DIAGRAM
The following terms apply to the block diagram:
•
y is the process signal
•
r is the setpoint signal
•
w is the tracking signal
•
u is the regulator output
•
K is the proportional gain
•
b is the setpoint weighting
•
T
d
is the derivative time constant
•
N is the derivative limit
•
T
i
is the integral time constant
•
T
t
is the anti-windup time constant
•
s is the domain
In discrete form, the equations for the regulator are:
(EQ 5.27)
Where
T
S
is the sampling time and AW is a flag which enables anti-windup. The incremental form of the above equation is:
(EQ 5.28)
Where:
y
r
w
+
-
e
K
T
i
+
+
1
s
1
T
t
+
-
i
+
+
+
d
u
sKT
d
1+sT /N
d
+
-1
b
+
p
K
832031A1.cdr
e k
( )
r k
( )
y k
( )
–
=
p k
( )
K br k
( )
y k
( )
–
(
)
=
d k
( )
T
d
T
d
NT
S
+
------------------------
d k
1
–
(
)
×
kT
d
N
T
d
NT
S
+
------------------------
y k
( )
y k
1
–
(
)
–
(
)
×
–
=
u k
( )
p k
( )
i k
( )
d k
( )
+
+
=
i k
1
+
(
)
i k
( )
KT
S
e k
( )
T
i
-----------------------
T
S
T
t
------
w k
( )
u k
( )
–
(
)
AW
×
×
+
+
=
Du k
( )
u k
( )
u k
1
–
(
)
–
=
Dp k
( )
Di k
( )
Dd k
( )
+
+
=
Summary of Contents for UR F35 Series
Page 10: ...x F35 Multiple Feeder Protection System GE Multilin TABLE OF CONTENTS ...
Page 366: ...5 238 F35 Multiple Feeder Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 426: ...10 12 F35 Multiple Feeder Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 454: ...A 28 F35 Multiple Feeder Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 620: ...F 12 F35 Multiple Feeder Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 630: ...H 8 F35 Multiple Feeder Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 640: ...x F35 Multiple Feeder Protection System GE Multilin INDEX ...