GE Multilin
F35 Multiple Feeder Protection System
B-31
APPENDIX B
B.4 MEMORY MAPPING
B
4142
DNP Object 20 Default Variation
0 to 3
---
1
F523
0 (1)
4143
DNP Object 21 Default Variation
0 to 3
---
1
F524
0 (1)
4144
DNP Object 22 Default Variation
0 to 3
---
1
F523
0 (1)
4145
DNP Object 23 Default Variation
0 to 3
---
1
F523
0 (1)
4146
DNP Object 30 Default Variation
1 to 5
---
1
F001
1
4147
DNP Object 32 Default Variation
0 to 5
---
1
F525
0 (1)
4148
SCADA Protocol
0 to 2
---
1
F629
0 (DNP 3.0)
Communications Actual Values (Read Only)
4160
Modbus Available TCP/IP Connections
0 to 4
---
1
F001
4
4161
DNP Available TCP/IP Connections
0 to 2
---
1
F001
2
4162
IEC Available TCP/IP Connections
0 to 2
---
1
F001
2
4163
MMS Available TCP/IP Connections
0 to 5
---
1
F001
5
4164
PMU Available TCP/IP Connections
0 to 4
---
1
F001
4
Simple Network Time Protocol (Read/Write Setting)
4168
Simple Network Time Protocol (SNTP) Function
0 to 1
---
1
F102
0 (Disabled)
4169
Simple Network Time Protocol (SNTP) Server IP Address
0 to 4294967295
---
1
F003
0
416B
Simple Network Time Protocol (SNTP) UDP Port Number
1 to 65535
---
1
F001
123
Data Logger Commands (Read/Write Command)
4170
Data Logger Clear
0 to 1
---
1
F126
0 (No)
Data Logger (Read/Write Setting)
4181
Data Logger Channel Settings (16 items)
---
---
---
F600
0
4191
Data Logger Mode
0 to 1
---
1
F260
0 (Continuous)
4192
Data Logger Trigger
0 to 4294967295
---
1
F300
0
4194
Data Logger Rate
15 to 3600000
ms
1
F003
60000
Clock (Read/Write Setting)
419F
Synchronizing Source
0 to 3
---
1
F623
0 (None)
Clock (Read/Write Command)
41A0
Real Time Clock Set Time
0 to 235959
---
1
F050
0
Clock (Read/Write Setting)
41A2
SR Date Format
0 to 4294967295
---
1
F051
0
41A4
SR Time Format
0 to 4294967295
---
1
F052
0
41A6
IRIG-B Signal Type
0 to 2
---
1
F114
0 (None)
41A7
Clock Events Enable / Disable
0 to 1
---
1
F102
0 (Disabled)
41A8
Time Zone Offset from UTC
–24 to 24
hours
0.5
F002
0
41A9
Daylight Savings Time (DST) Function
0 to 1
---
1
F102
0 (Disabled)
41AA
Daylight Savings Time (DST) Start Month
0 to 11
---
1
F237
0 (January)
41AB
Daylight Savings Time (DST) Start Day
0 to 6
---
1
F238
0 (Sunday)
41AC
Daylight Savings Time (DST) Start Day Instance
0 to 4
---
1
F239
0 (First)
41AD
Daylight Savings Time (DST) Start Hour
0 to 23
---
1
F001
2
41AE
Daylight Savings Time (DST) Stop Month
0 to 11
---
1
F237
0 (January)
41AF
Daylight Savings Time (DST) Stop Day
0 to 6
---
1
F238
0 (Sunday)
41B0
Daylight Savings Time (DST) Stop Day Instance
0 to 4
---
1
F239
0 (First)
41B1
Daylight Savings Time (DST) Stop Hour
0 to 23
---
1
F001
2
Fault Report Commands (Read/Write Command)
41B2
Fault Reports Clear Data Command
0 to 1
---
1
F126
0 (No)
Oscillography (Read/Write Setting)
41C0
Oscillography Number of Records
3 to 64
---
1
F001
5
41C1
Oscillography Trigger Mode
0 to 1
---
1
F118
0 (Auto.
Overwrite)
41C2
Oscillography Trigger Position
0 to 100
%
1
F001
50
41C3
Oscillography Trigger Source
0 to 4294967295
---
1
F300
0
41C5
Oscillography AC Input Waveforms
0 to 4
---
1
F183
2 (16 samples/
cycle)
41D0
Oscillography Analog Channel
n
(16 items)
0 to 65535
---
1
F600
0
4200
Oscillography Digital Channel
n
(63 items)
0 to 4294967295
---
1
F300
0
Table B–10: MODBUS MEMORY MAP (Sheet 23 of 64)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for UR F35 Series
Page 10: ...x F35 Multiple Feeder Protection System GE Multilin TABLE OF CONTENTS ...
Page 366: ...5 238 F35 Multiple Feeder Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 426: ...10 12 F35 Multiple Feeder Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 454: ...A 28 F35 Multiple Feeder Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 620: ...F 12 F35 Multiple Feeder Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 630: ...H 8 F35 Multiple Feeder Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 640: ...x F35 Multiple Feeder Protection System GE Multilin INDEX ...