Chapter 6. Service Request Function
GFK-2950C
February 2018
301
6.16
SVC_REQ 15: Read Last-Logged Fault Table Entry
Use SVC_REQ 15 to read the last entry logged in the Controller Fault Table or the I/O Fault Table. The
SVC_REQ output is set ON unless some invalid number is entered as the requested operation or the
fault table is empty.
The non-extended parameter block has a length of 22 words and the extended parameter block has
a length of 24 words.
Input Parameter Block
Address
Format
0
0 = Read Controller Fault Table
1 = Read I/O Fault Table
80h = Read extended Controller Fault Table
81h = Read extended I/O Fault Table
Output Parameter Block
The format of the output parameter block depends on whether SVC_REQ 15 reads the Controller
Fault Table, the extended Controller Fault Table, the I/O Fault Table or the extended I/O Fault Table.
Controller Fault Table Output Format
Address
I/O Fault Table Output Format
High Byte
Low Byte
High Byte
Low Byte
0
0
1
unused
long/short (always 01)
1
reference address
memory type
long/short
(always 03)
unused
unused
2
reference address offset
slot
rack
3
slot
rack
task
4
block
bus
fault action
fault group
5
point
error code
6
fault action
fault group
fault extra data
7
fault type
fault category
8 to
18
fault extra data
fault description
minutes
seconds
19
minutes
seconds
day of month
hour
20
day of month
hour
year
month
21
year
month
milliseconds
(extended format only)
22
milliseconds
(extended format only)
not used
(extended format only)
23
not used
(extended format only)
Summary of Contents for PACSystems RSTi-EP