Chapter 9. Diagnostics
GFK-2950C
February 2018
405
11 hex/17 decimal, LAN Softswitch/Modem mismatch
Configuration of LAN module does not match modem type or configuration programmed by
softswitch utility.
Correction
1)
Correct configuration of modem type.
2)
Consult LAN Interface manual for configuration setup.
13 hex/19 decimal, DCD Length Mismatch
Directed control data lengths do not match.
Correction
See Fault Extra Data.
Fault Extra Data for DCD Length Mismatch
Byte Value
[0]
FF
[1]
Bus address
[2]
Module’s directed data length
[3]
Configured module’s directed data length
25 hex/37 decimal, Controller Reference Out-of-Range
A reference on either the trigger, disable, or I/O specification is out of the configured limits.
Correction
Modify the incorrect reference to be within range, or increase the configured size of the reference
data.
26 hex/38 decimal, Bad Program Specification
The I/O specification of a program is corrupted.
Correction
Contact Technical Support.
27 hex/39 decimal, Unresolved or Disabled Interrupt Reference
The CPU generates this error when an interrupt trigger reference is either out of range or disabled in
the I/O module’s configuration.
Correction
1)
Remove or correct the interrupt trigger reference.
2)
Update the configuration file to enable this particular interrupt.
43 hex/67 decimal, Module Configuration Failure
Module configuration was not successfully accepted by the module.
Correction
Check fault table for other module-specific faults for possible reasons why the module did not accept
the configuration. Check that the configuration for the module is correct and valid.
4B hex/75 decimal, ECC jumper is disabled, but should be enabled
If the CPU redundancy feature is supported and required, the ECC jumper must be in the enabled
position.