CHAPTER 2: INSTALLATION
ELECTRICAL
PQM POWER QUALITY METER – INSTRUCTION MANUAL
2–13
For a single-phase connection, connect current and voltage to the phase A inputs only. All
other inputs are ignored. Select the
S2 SYSTEM SETUP \ CURRENT/VOLTAGE
CONFIGURATION \ VT WIRING:
SINGLE PHASE setpoint.
FIGURE 2–9: Single Phase Connection
The figure below shows two methods for connecting CTs to the PQM for a 3-wire system.
The top drawing shows the standard wiring configuration using three CTs. An alternate
wiring configuration uses only two CTs. With the two CT method, the third phase is