CHAPTER 7: MODBUS COMMUNICATIONS
MODBUS MEMORY MAP
PQM POWER QUALITY METER – INSTRUCTION MANUAL
7–57
ANALOG
INPUT
continued
10A9
Analog Input Alt Relay
0-4
1
---
F29
0=OFF
10AA
Analog Input Alt Level
0 to 65000
1
---
F1
0
10AB
Analog Input Alt Delay
5 to 6000
5
0.1 x s
F1
100=10.0 s
10AC
Reserved
10AD
Reserved
10AE
Reserved
10AF
Reserved
Table 7–10: PQM Memory Map (Sheet 41 of 55)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS and
SCALE
FORMAT
FACTORY
DEFAULT
Notes:* Data type depends on the Command Operation Code.** Any valid Actual Values or Setpoints address.
*** Maximum Setpoint value represents “OFF”.**** Minimum Setpoint value represents “OFF”.
***** Maximum Setpoint value represents “UNLIMITED”.****** Applicable to older revisions with VFD display only