PQM POWER QUALITY METER – INSTRUCTION MANUAL
MODBUS MEMORY MAP
CHAPTER 7: MODBUS COMMUNICATIONS
SIMULATION
11C8
Current/Voltage Simulation
0 to 1
1
---
F11
0=OFF
11C9
Current/Voltage Simulation Time
5 to 305
5
min
F1
*****
15 min
11CA
Phase A Current
0 to 10000
1
A
F1
0 A
11CB
Phase B Current
0 to 10000
1
A
F1
0 A
11CC
Phase C Current
0 to 10000
1
A
F1
0 A
11CD
Neutral Current
0 to 10000
1
A
F1
0 A
11CE
Vax Voltage
0 to 65000
1
V
F1
0 V
11CF
Vbx Voltage
0 to 65000
1
V
F1
0 V
11D0
Vcx Voltage
0 to 65000
1
V
F1
0 V
11D1
Phase Angle
0 to 359
1
degrees
F1
0 degrees
11D2
Analog Output Simulation
0 to 1
1
---
F11
0=OFF
11D3
Analog Output Simulation Time
5 to 305
5
min
F1
*****
15 min
11D4
Analog Output 1
0 to
1201***
1
0.1 x %
F1
1201=OFF
11D5
Analog Output 2
0 to
1201***
1
0.1 x %
F1
1201=OFF
11D6
Analog Output 3
0 to
1201***
1
0.1 x %
F1
1201=OFF
11D7
Analog Output 4
0 to
1201***
1
0.1 x %
F1
1201=OFF
11D8
Analog Input Simulation
0 to 1
1
---
F11
0=OFF
11D9
Analog Input Simulation Time
5 to 305
5
min
F1
*****
15 min
11DA
Analog Input
40 to 201
1
0.1 x mA
F1
201=OFF
11DB
Switch Input Simulation
0 to 1
1
---
F11
0=OFF
11DC
Switch Input Simulation Time
5 to 305
5
min
F1
*****
15 min
11DD
Switch Input A
0 to 1
1
---
F27
0=OPEN
11DE
Switch Input B
0 to 1
1
---
F27
0=OPEN
11DF
Switch Input C
0 to 1
1
---
F27
0=OPEN
11E0
Switch Input D
0 to 1
1
---
F27
0=OPEN
11E1
Reserved
11E2
Reserved
11E3
Reserved
TIME
ALARM
11E4
Time Relay
0 to 4
1
---
F29
0=OFF
11E5
Pickup Time Hours/Minutes
0 to 65535
1
hr/min
F22
12:00
11E6
Pickup Time Seconds
0 to 59000
1000
ms
F1
0
11E7
Dropout Time Hours/Minutes
0 to 65535
1
hr/min
F22
12:00
11E8
Dropout Time Seconds
0 to 59000
1000
ms
F1
0
11E9
Reserved
to
↓
↓
↓
↓
↓
↓
11EF
Reserved
Table 7–10: PQM Memory Map (Sheet 50 of 55)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS and
SCALE
FORMAT
FACTORY
DEFAULT
Notes:* Data type depends on the Command Operation Code.** Any valid Actual Values or Setpoints address.
*** Maximum Setpoint value represents “OFF”.**** Minimum Setpoint value represents “OFF”.
***** Maximum Setpoint value represents “UNLIMITED”.****** Applicable to older revisions with VFD display only