8–12
PQM POWER QUALITY METER – INSTRUCTION MANUAL
DNP 3.0 PROTOCOL
CHAPTER 8: DNP COMMUNICATIONS
12
0244
Neutral Current
1000ths of
nominal
20 units
F1
1
13
0245
Current Unbalance
tenths of 1
percent
10 units
F1
2
14
0280
Voltage Van
1000ths of
nominal V
10 units
F3
1
15
0282
Voltage Vbn
1000ths of
nominal V
10 units
F3
1
16
0284
Voltage Vcn
1000ths of
nominal V
10 units
F3
1
17
0286
Average Phase Voltage
1000ths of
nominal V
10 units
F3
1
18
0288
Voltage Vab
1000ths of
nominal V
10 units
F3
1
19
028A
Voltage Vbc
1000ths of
nominal V
10 units
F3
1
20
028C
Voltage Vca
1000ths of
nominal V
10 units
F3
1
21
028E
Average Line Voltage
1000ths of
nominal
10 units
F3
1
22
0290
Voltage Unbalance
0.1 x %
10 units
F1
2
23
02F0
3 Phase Real Power
1000ths of
nominal VA
20 units
F4
2
24
02F2
3 Phase Reactive Power
1000ths of
nominal VA
20 units
F4
2
25
02F4
3 Phase Apparent
Power
1000ths of
nominal VA
20 units
F3
2
26
02F6
3 Phase Power Factor
%
10 units
F2
2
27
02F7
Phase A Real Power
1000ths of
nominal
20 units
F4
3
28
02F9
Phase A Reactive Power
1000ths of
nominal
20 units
F4
3
29
02FB
Phase A Apparent
Power
1000ths of
nominal
20 units
F3
3
30
02FD
Phase A Power Factor
%
10 units
F2
3
Table 8–4: Point List for Analog Input/Output Change (Sheet 2 of 9)
POINT
MOBUS
REG
DESCRIPTION
UNIT /
VALUE
DEADBAND
FORMAT
CODE
EVENT
CLASS
ASSIGNED
TO
see footnote explanations at the end of the table