CHAPTER 4: CONNECTING TO DEVICES AND NETWORKS
D400 SUBSTATION GATEWAY INSTRUCTION MANUAL
GE INFORMATION
71
D400 connection to DNP3 I/O modules
To configure a D400 to operate with a DNP3 I/O module.
1.
Log in to the D400.
Result: The D400 HMI appears.
Refer to the D400 online help for detailed information on the D400 HMI.
2.
Create the Device Type:
2.1.
Click the
Configuration
powerbar
button.
2.2.
Click
Client Map
.
2.3.
Click
New
to create a new device map file.
Result: The Map File window appears.
2.4.
Select
DNP
and click
OK
.
2.5.
In the left-hand pane, configure the device point settings.
2.6.
In the right-hand pane, configure the device polling parameters.
2.7.
Click
Save
.
3.
Configure the DNP3 serial port parameters:
3.1.
Click
Connections
.
3.2.
Click
Add Connection
.
Result: The New Connection window appears.
3.3.
Select
Serial Connection
and select
DNP Multidrop
on the Serial Configuration
Type drop-down list.
3.4.
Configure the connection as required. For
Map File
, select the client map file
you created in Step 2.
3.5.
Click
Save Configuration
.
Refer to Appendix B for DNP3 I/O module installation instructions.
D400 system redundancy
A redundant D400 setup allows a secondary D400 to automatically take over operations
from a paired D400 unit that has failed.
D400 equipment redundancy requires two D400 units and zero, one, or two RS232 switch
panels.
NOTE
The RS-232 switch panel is optional for Warm and Hot Standby redundancy.
A pair of LEDs marked
CCU A
and
CCU B
indicate which of the D400 units is currently active.
If the hardware or software of the active unit fails, it is automatically switched offline and
serial connections to the field are transferred to the standby unit. A toggle switch on the
RS232 switch panel can be used to switch the D400 devices between active and standby
modes.
Failover sequence
If the active D400 unit fails, the following actions occur:
1.
The standby D400 unit detects the failure through the lack of a heartbeat signal on the
ping cable or through a status change on the watchdog cable.
Summary of Contents for Multilin D400
Page 12: ...12 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL PRODUCT SUPPORT ...
Page 28: ...28 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL CHAPTER 1 BEFORE YOU START ...
Page 34: ...34 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL CHAPTER 2 INSTALLING THE D400 ...
Page 88: ...88 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL CHAPTER 5 POWERING UP THE D400 ...
Page 174: ...174 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL APPENDIX A STANDARDS PROTECTION ...
Page 184: ...184 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL APPENDIX C LIST OF ACRONYMS ...
Page 192: ...192 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL INDEX ...