CHAPTER 8: USING THE D400
D400 SUBSTATION GATEWAY INSTRUCTION MANUAL
GE INFORMATION
111
System status points
You can obtain status information about your D400 through several system points. These
points can be viewed through the
Application
tab on the Point Summary window.
Table 26: D400 System Status Points
NOTE
FPGA Version 1.10 or above is required to provide system status points for the power
supplies and 100BASE-FX card. In previous FPGA versions, these points appear as offline
regardless of their actual status. If your FPGA version is 1.09 or less, please contact Product
Support.
Name
Data Type
Description
Power Supply 1 Good
Digital Input
Value is 1 when a failure has occurred or the power
supply is not installed. Because this point remains
online even when the power supply is not installed, you
can force the point for the missing supply to the offline
state or you can apply a tag indicating that the unit is
not installed.
Power Supply 2 Good
Digital Input
IRIG-B Enabled
Digital Input
Value is 1 when enabled
IRIG-B Watchdog Expired Digital Input
Value is 1 when expired
Front Port Link Good
Digital Input
Value is 1 when true
Note that “Active” is not the same as “Activity”. It is used
in the same sense as Active and Standby for redundant
Ethernet configurations. The point does not flicker on
and off in the same way that the activity LED does for
an Ethernet port.
The actual number of ports available depend on the
configured options of the
D400
unit. Points associated
with unavailable ports are made offline and invalid.
NET1 Port 1 Link Good
Digital Input
NET1 Port 1 Active
Digital Input
NET1 Port 2 Link Good
Digital Input
NET1 Port 2 Active
Digital Input
NET1 Port 3 Link Good
Digital Input
NET1 Port 3 Active
Digital Input
NET1 Port 4 Link Good
Digital Input
NET1 Port 4 Active
Digital Input
NET2 Port 1 Link Good
Digital Input
NET2 Port 1 Active
Digital Input
NET2 Port 2 Link Good
Digital Input
NET2 Port 2 Active
Digital Input
NET2 Port 3 Link Good
Digital Input
NET2 Port 3 Active
Digital Input
NET2 Port 4 Link Good
Digital Input
NET2 Port 4 Active
Digital Input
System PLD Revision
Analog Input
A string that describes the revision or ID number of the
specified component.
Main Board ID
Analog Input
Mid-Plane ID
Analog Input
NET1 Card ID
Analog Input
NET2 Card ID
Analog Input
USB KVM Card ID
Analog Input
Summary of Contents for Multilin D400
Page 12: ...12 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL PRODUCT SUPPORT ...
Page 28: ...28 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL CHAPTER 1 BEFORE YOU START ...
Page 34: ...34 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL CHAPTER 2 INSTALLING THE D400 ...
Page 88: ...88 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL CHAPTER 5 POWERING UP THE D400 ...
Page 174: ...174 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL APPENDIX A STANDARDS PROTECTION ...
Page 184: ...184 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL APPENDIX C LIST OF ACRONYMS ...
Page 192: ...192 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL INDEX ...