GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL
APPENDIX B INSTALLING AND CONNECTING DNP3 I/O MODULES
Connecting DNP3 I/O modules (High Voltage)
For a High-Voltage (HV) DNP I/O Module, for example: WESTERM D20SZ (517-0249-ML):
1.
Interconnect the DNP3 link cabling between each DNP3 I/O module.
2.
Connect pins 1 and 2 (and also pins 3 and 4 if a redundant power supply is used) on
TB2 to an External Power Supply (40 to 150 VDC) as shown in Figure 72.
Figure 72: Interconnect cabling between each DNP3 I/O module and power (HV)
NOTE
The location of the External (Ext) Power Supply terminal varies between WESTERM I/O
module types.
Connecting to a D400
When connecting the DNP3 I/O modules to the D400, configure the D400 port for 2-wire
mode. Refer to section: “RS-485 connections” on page 58 which indicates the
corresponding cable connections.
To D400 (RTU Master)
To Field Equipment
To Field Equipment
To Field Equipment
To Ext Power
To Ext Power
To Ext Power
To Ext Power
Cable: D400 (RTU Master)
GE Part Number: 977-0503
External DNP 3
I/O Module
Power Supply
Summary of Contents for Multilin D400
Page 12: ...12 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL PRODUCT SUPPORT ...
Page 28: ...28 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL CHAPTER 1 BEFORE YOU START ...
Page 34: ...34 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL CHAPTER 2 INSTALLING THE D400 ...
Page 88: ...88 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL CHAPTER 5 POWERING UP THE D400 ...
Page 174: ...174 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL APPENDIX A STANDARDS PROTECTION ...
Page 184: ...184 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL APPENDIX C LIST OF ACRONYMS ...
Page 192: ...192 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL INDEX ...